5<br />

Vent Information and Diagrams<br />

A. Vent Table Key<br />

The abbreviations listed in this vent table key are used in<br />

the vent diagrams.<br />

Symbol<br />

V1<br />

V2<br />

Description<br />

First section (closest to appliance of vertical length<br />

Second section of vertical length<br />

Vertical<br />

12 in.<br />

8-1/2 in.<br />

H1<br />

First section (closest to appliance) of horizontal length<br />

8-1/2 in.<br />

H2<br />

Second section of horizontal length<br />

B. Use of Elbows<br />

WARNING<br />

Fire Hazard.<br />

Explosion Risk.<br />

Asphyxiation Risk.<br />

Do NOT connect this gas appliance to a<br />

chimney fl ue serving a separate solid-fuel or<br />

gas burning appliance.<br />

• Vent this appliance directly outside.<br />

• Use separate vent system for this appliance.<br />

May impair safe operation of this appliance or<br />

other appliances connected to the fl ue.<br />

CAUTION<br />

ALL vent confi guration specifi cations MUST be followed.<br />

• This product is tested and listed to these<br />

specifi cations.<br />

• Appliance performance will suffer if specifi cations are<br />

not followed.<br />

Diagonal runs have both vertical and horizontal vent aspects<br />

when calculating the effects. Use the rise for the<br />

vertical aspect and the run for the horizontal aspect (see<br />

Figure 5.1).<br />

Two 45 0 elbows may be used in place of one 90 0 elbow. On<br />

45 0 runs, one foot of diagonal is equal to 8.5 inches horizontal<br />

run and 8.5 inches vertical run. A length of straight<br />

pipe is allowed between two 45 0 elbows (see Figure 5.1).<br />

Figure 5.1<br />

C. Measuring Standards<br />

Vertical and horizontal measurements listed in the vent<br />

diagrams were made using the following standards.<br />

1. Pipe measurements are shown using the effective length<br />

of pipe (see Figure 5.2).<br />

2. Measurements are made from the appliance outer wrap,<br />

not from the standoffs.<br />

3. Horizontal terminations are measured to the outside<br />

mounting surface (flange of termination cap) (see Figure<br />

4.1).<br />

4. Vertical terminations are measured to bottom of termination<br />

cap.<br />

5. Horizontal pipe installed level with no rise.<br />

Figure 5.2<br />

Horizontal<br />

Effective<br />

Height/Length<br />

DVP Pipe Effective Length<br />

Pipe<br />

Length/<br />

Inches<br />

DVP4 4<br />

DVP6 6<br />

DVP12 12<br />

DVP24 24<br />

DVP36 36<br />

DVP48 48<br />

DVP6A 3 to 6<br />

DVP12A 3 to 12<br />

DVP12MI 3 to 12<br />

DVP24MI 3 to 24<br />

12<br />

Heat & Glo • Bravo • 704-902 Rev. D • 5/08