Configuration<br />

Output 2<br />

Temperature unit and probe. Output current.<br />

Menu group<br />

Output 2 o2.<br />

Code Display<br />

Select menu item<br />

Select °C/°F<br />

Select temperature probe<br />

Select 0-20 / 4-20 mA<br />

Enter current beginning<br />

Enter current end<br />

Set output filter<br />

22 mA for temp error<br />

Hold mode<br />

Code Display Action Choices<br />

o2. Specify temperature unit<br />

Select with key<br />

Proceed with enter<br />

Select temperature probe<br />

Select with key<br />

Proceed with enter<br />

Set output current range<br />

Select with key<br />

Proceed with enter<br />

Current beginning:<br />

Enter lower end of scale.<br />

Select with key, edit number<br />

with key, proceed with enter<br />

Current end:<br />

Enter upper end of scale.<br />

Select with key, edit number<br />

with key, proceed with enter<br />

°C<br />

(°F)<br />

22NTC<br />

(30NTC)<br />

4 - 20 mA<br />

0 - 20 mA<br />

000.0 °C<br />

100.0 °C<br />

Process temperature: Current beginning and current end<br />

Example 1: Range 0 to 100 °C<br />

[°C]<br />

100 Process temperature<br />

Example 2: Range 50 to 70 °C.<br />

Advantage: Higher resolution in<br />

range of interest<br />

[°C]<br />

70<br />

Process temperature<br />

End:<br />

Press conf, then enter<br />

38 O 2 4100 e<br />

0<br />

4<br />

Output current<br />

20<br />

[mA]<br />

50<br />

4<br />

Output current<br />

20 [mA]<br />

39