Performance <strong>and</strong><br />

functionality<br />

Micrologic control units<br />

Overview of functions<br />

All Masterpact <strong>circuit</strong> <strong>breakers</strong> can be<br />

equipped with a Micrologic control unit.<br />

Control units are designed to protect Power<br />

<strong>circuit</strong>s <strong>and</strong> loads. Alarms may be<br />

programmed for remote indications.<br />

Measurements of current, voltage,<br />

frequency, <strong>power</strong> <strong>and</strong> <strong>power</strong> quality<br />

optimise continuity of service <strong>and</strong> energy<br />

management.<br />

Dependability<br />

The use of an ASIC electronic component for protection functions in all Micrologic<br />

control units, guarantees a high degree of reliability <strong>and</strong> immunity to conducted or<br />

radiated disturbances.<br />

On Micrologic A, P <strong>and</strong> H* control units, advanced functions are managed by an<br />

independent microprocessor.<br />

Micrologic name codes<br />

5.0 A<br />

X Y Z<br />

t<br />

Micrologic 5: selective protection<br />

X: type of protection<br />

c 5 for selective protection.<br />

c 6 for selective + earth-fault protection.<br />

c 7 for selective + earth-leakage protection.<br />

Y: control-unit generation<br />

Identification of the control-unit generation.<br />

“0” signifies the first generation.<br />

Z: type of measurement<br />

c A for “ammeter”.<br />

c P for “<strong>power</strong> meter”.<br />

0 Ir Isd Ii I<br />

t<br />

Protection:<br />

long time + short time + instantaneous<br />

Micrologic 6: selective + earth-fault protection<br />

t<br />

0 Ir Isd Ii I<br />

0 Ig<br />

I<br />

Protection:<br />

long time<br />

+ short time<br />

+ instantaneous<br />

+ earth fault<br />

Micrologic 7: selective + earth-leakage protection<br />

t<br />

t<br />

0 Ir Isd Ii I<br />

0 I∆n I<br />

Protection:<br />

long time<br />

+ short time<br />

+ instantaneous<br />

+ earth leakage<br />

* Availability to be announced<br />