Functions<br />
<strong>and</strong> characteristics<br />
Communication<br />
Masterpact in a communication<br />
network<br />
Devices<br />
Circuit <strong>breakers</strong> equipped with Micrologic control units may be connected to either<br />
a Digipact or Modbus communication bus. The information made available<br />
depends on the type of Micrologic control unit (A, P or H) <strong>and</strong> on the type of<br />
communication bus (Digipact or Modbus).<br />
Switch-<strong>disconnectors</strong> may be connected exclusively to the Digipact communication<br />
bus.<br />
Communication bus<br />
Digipact bus<br />
The Digipact bus is the internal bus of the low-voltage <strong>switch</strong>board in which the<br />
Digipact communicating devices are installed (Masterpact with Digipact COM,<br />
PM150, SC150, UA150, etc.). This bus must be equipped with a DC150 data<br />
concentrator (see the Powerlogic System catalogue).<br />
Addresses<br />
Addressing is carried out by the DC150 data concentrator.<br />
Number of devices<br />
The maximum number of devices that may be connected to the Digipact bus is<br />
calculated in terms of “communication points”. These points correspond to the<br />
amount of traffic the bus can h<strong>and</strong>le. The total number of points for the various<br />
devices connected to a single bus must not exceed 100.<br />
If the required devices represent more than 100 points, add a second Digipact<br />
internal bus.<br />
Communicating device Number of points<br />
DC150 data concentrator 4<br />
Micrologic + Digipact COM 4<br />
PM150 4<br />
SC150 4<br />
UA150 4<br />
Length of bus<br />
The maximum recommended length for the Digipact internal bus is 200 meters.<br />
Bus <strong>power</strong> source<br />
Power is supplied by the DC150 data concentrator (24 V)..<br />
30