Performance <strong>and</strong><br />
functionality<br />
Remote operation<br />
Remote ON / OFF<br />
Two solutions are available for remote<br />
operation of Masterpact devices:<br />
c A Hard wired solution.<br />
c A bus solution with the ‘COM’<br />
communication option.<br />
The remote ON / OFF function is used to remotely open <strong>and</strong> close the <strong>circuit</strong><br />
breaker. It comprises:<br />
c A gear motor (MCH) equipped with a ‘springs charged’ limit <strong>switch</strong> contact (CH).<br />
c Two voltage releases:<br />
v A closing release (XF).<br />
v An opening release (MX).<br />
Optionally, other functions may be added:<br />
c A ‘ready to close’ contact (PF).<br />
c An electrical closing pushbutton (BPFE).<br />
c Remote reset following a fault (RAR).<br />
A remote-operation function is generally combined with:<br />
c Device ON / OFF indication (OF).<br />
c ‘fault-trip’ indication (SDE).<br />
Wiring diagram of a point-to-point remote ON / OFF function<br />
spring<br />
charged<br />
opening<br />
order<br />
closing<br />
order<br />
ready<br />
to close<br />
fault<br />
open<br />
closed<br />
B3<br />
B2<br />
C2<br />
A2<br />
252 254<br />
82 84<br />
12 14<br />
MCH<br />
PF<br />
OF1<br />
MX<br />
XF<br />
SDE<br />
CH<br />
B1<br />
C1<br />
A1<br />
251<br />
81<br />
11<br />
Wiring diagram of a bus-type remote ON / OFF function<br />
spring<br />
charged<br />
opening<br />
order<br />
closed<br />
order<br />
B3<br />
B2<br />
C2<br />
C3<br />
A2<br />
A3<br />
MCH<br />
CH<br />
MXcom<br />
XFcom<br />
Note:<br />
An opening order always takes priority over a closing<br />
order.<br />
If opening <strong>and</strong> closing orders occur simultaneously(when<br />
in the open position), the mechanism discharges without<br />
any movement of the main contacts. The <strong>circuit</strong> breaker<br />
remains in the open position (OFF).<br />
In the event of maintained opening <strong>and</strong> closing orders,<br />
the st<strong>and</strong>ard mechanism provides an anti-pumping<br />
function by maintaining the main contacts in the open<br />
position.<br />
After tripping or opening using the manual or electrical<br />
controls, the closing coil must first be reset before reclosing<br />
can take place.<br />
When the ‘automatic reset after fault trip (RAR)’ option is<br />
installed, it is impotant to ensure that the automatic/<br />
remote closing system is designed to prevent Autoreclosing<br />
under fault trip conditions.<br />
B1<br />
OF<br />
PF<br />
SDE<br />
CH<br />
C1<br />
A1<br />
COM<br />
supervisor<br />
(i.e. PowerLogic software)<br />
38