Performance <strong>and</strong><br />

functionality<br />

Remote operation<br />

Remote ON / OFF<br />

Two solutions are available for remote<br />

operation of Masterpact devices:<br />

c A Hard wired solution.<br />

c A bus solution with the ‘COM’<br />

communication option.<br />

The remote ON / OFF function is used to remotely open <strong>and</strong> close the <strong>circuit</strong><br />

breaker. It comprises:<br />

c A gear motor (MCH) equipped with a ‘springs charged’ limit <strong>switch</strong> contact (CH).<br />

c Two voltage releases:<br />

v A closing release (XF).<br />

v An opening release (MX).<br />

Optionally, other functions may be added:<br />

c A ‘ready to close’ contact (PF).<br />

c An electrical closing pushbutton (BPFE).<br />

c Remote reset following a fault (RAR).<br />

A remote-operation function is generally combined with:<br />

c Device ON / OFF indication (OF).<br />

c ‘fault-trip’ indication (SDE).<br />

Wiring diagram of a point-to-point remote ON / OFF function<br />

spring<br />

charged<br />

opening<br />

order<br />

closing<br />

order<br />

ready<br />

to close<br />

fault<br />

open<br />

closed<br />

B3<br />

B2<br />

C2<br />

A2<br />

252 254<br />

82 84<br />

12 14<br />

MCH<br />

PF<br />

OF1<br />

MX<br />

XF<br />

SDE<br />

CH<br />

B1<br />

C1<br />

A1<br />

251<br />

81<br />

11<br />

Wiring diagram of a bus-type remote ON / OFF function<br />

spring<br />

charged<br />

opening<br />

order<br />

closed<br />

order<br />

B3<br />

B2<br />

C2<br />

C3<br />

A2<br />

A3<br />

MCH<br />

CH<br />

MXcom<br />

XFcom<br />

Note:<br />

An opening order always takes priority over a closing<br />

order.<br />

If opening <strong>and</strong> closing orders occur simultaneously(when<br />

in the open position), the mechanism discharges without<br />

any movement of the main contacts. The <strong>circuit</strong> breaker<br />

remains in the open position (OFF).<br />

In the event of maintained opening <strong>and</strong> closing orders,<br />

the st<strong>and</strong>ard mechanism provides an anti-pumping<br />

function by maintaining the main contacts in the open<br />

position.<br />

After tripping or opening using the manual or electrical<br />

controls, the closing coil must first be reset before reclosing<br />

can take place.<br />

When the ‘automatic reset after fault trip (RAR)’ option is<br />

installed, it is impotant to ensure that the automatic/<br />

remote closing system is designed to prevent Autoreclosing<br />

under fault trip conditions.<br />

B1<br />

OF<br />

PF<br />

SDE<br />

CH<br />

C1<br />

A1<br />

COM<br />

supervisor<br />

(i.e. PowerLogic software)<br />