Performance <strong>and</strong><br />
functionality<br />
Communication<br />
Communication architecture<br />
The (COM) communication option is<br />
required for integration of the <strong>circuit</strong><br />
breaker or <strong>switch</strong>-disconnector in a<br />
supervision system.<br />
Masterpact uses Modbus or Jbus<br />
communications protocol for full<br />
compatibility with SMS PowerLogic<br />
(electrical network) management systems.<br />
An external gateway is available for<br />
communication over ethernet networks.<br />
COM communication option<br />
For fixed devices, the COM option comprises of a communication module installed<br />
within the device <strong>and</strong> supplied by a set of sensors (OF, SDE ,PF <strong>and</strong> CH microcontacts)<br />
kit for connection to XF <strong>and</strong> MX communicating voltage releases.<br />
For drawout devices, the COM option comprises of:<br />
c A communication module within in the device <strong>and</strong> supplied by a set of<br />
auxilliaries (OF, SDE, PF <strong>and</strong> CH micro-contacts) <strong>and</strong>/or a kit for connection to<br />
XF <strong>and</strong> MX communicating voltage releases.<br />
c A communication module installed on the chassis <strong>and</strong> supplied by a set of<br />
sensors (CE, CD <strong>and</strong> CT contacts).<br />
Each installed device has an address that is assigned via the keypad of the control<br />
unit (Modbus) or remotely (Batibus). The address of a drawout device is assigned<br />
to the chassis which maintains the same address if the device is replaced.<br />
Status indication by the COM option is independent of the auxiliary indication<br />
contacts. These contacts remain available for conventional uses.<br />
“Device” communication module<br />
This module is independent of the control unit. Installed in the device, behind the<br />
control unit, it receives <strong>and</strong> transmits information on the communication network.<br />
An infra-red link transmits data between the control unit <strong>and</strong> the communication<br />
module.<br />
Consumption: 100 mA.<br />
“Chassis” communication module<br />
Installed on the chassis, this module makes it possible to address the chassis <strong>and</strong><br />
to maintain the address when the <strong>circuit</strong> breaker is in the disconnected position.<br />
Consumption: 100 mA.<br />
XF <strong>and</strong> MX communicating voltage releases<br />
The XF <strong>and</strong> MX communicating voltage releases are equipped for connection to<br />
the “device” communication module.<br />
The remote-tripping function (second MX or MN) is independent of the<br />
communication option.<br />
Communication architecture<br />
E45183 056431<br />
Modbus «device»<br />
communication module<br />
Communication<br />
bus<br />
2<br />
OF<br />
SDE<br />
PF<br />
CH<br />
CD<br />
CCM modbus<br />
+ +<br />
+<br />
CT<br />
MX<br />
XF<br />
CE<br />
4<br />
5<br />
6<br />
1<br />
Modbus «chassis»<br />
communication module<br />
COM<br />
module<br />
3<br />
1 “Device” communication module<br />
2 “Chassis” communication module<br />
3 OF, SDE, PF <strong>and</strong> CH «device» auxilliaries<br />
4 CE, CD <strong>and</strong> CT «chassis» auxilliaries<br />
5 MX <strong>and</strong> XF releases<br />
28