Record vs. Snapshot a Preset<br />

Record and Snapshot are two different operations.<br />

Record will only use level information from Set Levels from the CEM+ modules in the group<br />

when storing a preset.<br />

Snapshot will use level information from all available sources to the CEM+ modules<br />

(DMXA, DMXB, EDMX, and Set Levels) when storing a preset.<br />

Activate/Deactivate a Preset<br />

Panic<br />

You can toggle any preset on or off from either the web interface or the face panel. Stations<br />

are also supported for preset activation, deactivation and recording. Please see<br />

Appendix B: SmartLink Stations Enabled on page 55 for more information on SmartLink<br />

stations.<br />

Max Active Presets<br />

Maximum Active Presets defines how many presets can be active in any one given room<br />

at a time. It can be set from a minimum of one (1) and to a maximum of four (4) at a time.<br />

Activating one preset more than allowable by Max Active Presets will deactivate the active<br />

preset with the lowest priority or if all active presets are at the same priority, the oldest<br />

previously activated priority.<br />

Max Active Presets defaults to one (1) which results in a “last action” activation/<br />

deactivation manner. (Turning on one preset turns off the previous preset.)<br />

Panic is configurable for different external switch action types (maintained vs. momentary)<br />

and switch resting states (normally-open vs. normally-closed). Panic always operates at the<br />

highest priority in the CEM+ and no other control source can pile-on with it or override it.<br />

Record Panic<br />

Create the desired panic look by setting <strong>dimmer</strong> levels from the CEM+ or from a external<br />

control source. Keep in mind that the Master Level acts as an intensity threshold for<br />

<strong>dimmer</strong>s and determines whether or not they are included in the panic. Only <strong>dimmer</strong>s with<br />

an intensity level equal to or greater than the Master Level will be included in Panic. When<br />

Panic is active, the <strong>dimmer</strong>s will also playback at the set Master Level.<br />

Set the Panic Master Level to your desired level (80% to 100%).<br />

Enable Force Others Off if you want load shedding to occur when Panic becomes active.<br />

What this means is when Panic becomes active, any <strong>dimmer</strong>s that are not included in Panic<br />

will be turned off.<br />

Lastly, record Panic.<br />

Activate Panic<br />

Panic can be activated via an external switch closure or locally via the face panel menu. It<br />

cannot be activated/deactivated via the web interface. Deactivation is also done by a switch<br />

closure (or lack of one, depending on the switch action type) or locally via the face panel<br />

menu.<br />