Table 6 displays the options that can be changed by the user.<br />
Table 6. Settings<br />
Description Available Settings Default Setting<br />
Change Language<br />
[English] [French] [German] [Spanish] [Japanese]<br />
[Simplified Chinese] [Russian] [Korean]<br />
[Traditional Chinese]<br />
English<br />
User Password<br />
Audible Alarms<br />
Set Date <strong>and</strong> Time<br />
Control Comm<strong>and</strong>s from Serial<br />
Port<br />
Output Voltage<br />
[Enabled] [Disabled]<br />
If Enabled, the default password is USER.<br />
NOTE: If you enter an incorrect password, the<br />
message “Wrong Password” appears. Press any<br />
button to return to the password screen <strong>and</strong> retry<br />
the password.<br />
[Enabled] [Disabled]<br />
NOTE: If you disable audible alarms, it takes effect<br />
instantly <strong>and</strong> remains disabled, even after a power<br />
cycle. This differs from the mute feature where the<br />
horn is temporarily silenced on any button press,<br />
but turns on again if a new alarm is triggered.<br />
Set Month, Day, Year, Hours, Minutes, <strong>and</strong> Seconds<br />
Date: mm/dd/yyyy<br />
Time: hh:mm:ss<br />
NOTE: The date format is dependent on the<br />
language selection.<br />
NOTE: Time is a 24-hour clock.<br />
[Enabled] [Disabled]<br />
If Enabled, control comm<strong>and</strong>s are accepted through<br />
the serial port, USB ports, or option card.<br />
If Disabled, configuration <strong>and</strong> load control<br />
comm<strong>and</strong>s are restricted to LCD only.<br />
[200V] [208V] [220V] [230V] [240V]<br />
[Auto-sensing]<br />
Disabled<br />
Enabled<br />
01/01/2009<br />
12:00:00<br />
Enabled<br />
Auto-sensing<br />
Output Frequency [50Hz] [60Hz] [Auto-sensing] Auto-sensing<br />