Retrieving the Event Log<br />
To retrieve the Event Log through the display:<br />
1 Press the button for one second to go to the main menu selection <strong>and</strong> scroll down to the<br />
Event Log menu using the button.<br />
2 Press the button to enter the Event Log list.<br />
3 Scroll through the listed events, notices, <strong>and</strong> alarms using either the button or the button.<br />
4 To return to the main menu, press the button for one second. The Event Log displays.<br />
5 Press the button. The <strong>UPS</strong> status screen displays.<br />
Behavior on Overload<br />
See Table 7 for an explanation of how the <strong>UPS</strong> responds to an overload condition.<br />
Table 7. Behavior on Overload<br />
Overload<br />
Load Level On Utility Power<br />
Severity<br />
Level 1<br />
Level 2<br />
Load 100% to<br />
101%<br />
Load 102% to<br />
110%<br />
Overload alarm only <strong>and</strong><br />
support load indefinitely<br />
Transfer to Bypass after<br />
12 seconds (±1 sec)<br />
If Bypass is not available,<br />
transfer to Fault mode after<br />
12 seconds (±1 sec)<br />
Level 3 Load > 110% Transfer to Bypass immediately<br />
If Bypass is not available,<br />
transfer to Fault mode in<br />
300 ms to 1 sec<br />
On Bypass/High<br />
Efficiency Mode<br />
Overload alarm only<br />
<strong>and</strong> support load<br />
indefinitely<br />
Transfer to Fault mode<br />
in 2 minutes (±1 sec)<br />
Transfer to Fault mode<br />
in 300 ms to 1 sec<br />
On Battery<br />
Overload alarm only,<br />
support load until low<br />
battery shutdown level<br />
is reached<br />
Transfer to Fault mode<br />
after 12 seconds<br />
(±1 sec) or until low<br />
battery shutdown level<br />
is reached<br />
Transfer to Fault mode<br />
in 300 ms to 1 sec<br />
48 | Operation