ENGINEERING DATA & DIMENSIONS<br />

MODELS <strong>REP</strong> 217-111 to <strong>REP</strong> 217-914<br />

19-5/8"<br />

8 BFW/GROOVED<br />

INLET<br />

8 BFW/GROOVED<br />

INLET<br />

2"<br />

ACCESS<br />

DOOR<br />

ACCESS<br />

DOOR<br />

55-1/2"<br />

50-3/4"<br />

H<br />

P<br />

B<br />

(2)3 MPT OVERFLOW<br />

(2)8 BFW/GROOVED<br />

OUTLET<br />

(2)2 MPT<br />

MAKE-UP<br />

(2)3 MPT<br />

DRAIN<br />

5-1/8"<br />

13/16"<br />

17' 4-1/8"<br />

23-1/8"<br />

15"<br />

7-1/2"<br />

63-3/4" 3/8"<br />

3-1/2"<br />

80-1/4"<br />

96-13/16"<br />

101-1/2"<br />

L<br />

Weights (LBS)<br />

Dimensions<br />

Fan<br />

Air<br />

Model Heaviest Motor Flow<br />

No. Shipping Operating Section (HP) (CFM) H † B P L<br />

<strong>REP</strong> 217-111 8700 15300 2220 (2) 7-1/2 91832 11’ 8-1/4” 7’ 3/4” 7’ 8-3/8” 10’ 5-1/4”<br />

<strong>REP</strong> 217-211 9340 15940 2540 (2) 7-1/2 90549 12’ 8-1/4” 8’ 3/4” 8’ 8-3/8” 10’ 5-1/4”<br />

<strong>REP</strong> 217-311 9400 16000 2540 (2) 10 99199 12’ 8-1/4” 8’ 3/4” 8’ 8-3/8” 10’ 5-1/4”<br />

<strong>REP</strong> 217-411 8900 15500 2230 (2) 15 114635 11’ 8-1/4” 7’ 3/4” 7’ 8-3/8” 10’ 5-1/4”<br />

<strong>REP</strong> 217-511 10100 16700 2890 (2) 10 97445 13’ 8-1/4” 9’ 3/4” 9’ 8-3/8” 10’ 5-1/4”<br />

<strong>REP</strong> 217-611 9540 16140 2540 (2) 15 112534 12’ 8-1/4” 8’ 3/4” 8’ 8-3/8” 10’ 5-1/4”<br />

<strong>REP</strong> 217-711 10240 16840 2890 (2) 15 110679 13’ 8-1/4” 9’ 3/4” 9’ 8-3/8” 10’ 5-1/4”<br />

<strong>REP</strong> 217-811 9640 16240 2540 (2) 20 123041 12’ 8-1/4” 8’ 3/4” 8’ 8-3/8” 10’ 5-1/4”<br />

<strong>REP</strong> 217-911 10400 17000 2890 (2) 25 129768 13’ 8-1/4” 9’ 3/4” 9’ 8-3/8” 10’ 5-1/4”<br />

Weights (LBS)<br />

Dimensions<br />

Fan<br />

Air<br />

Model Heaviest Motor Flow<br />

No. Shipping Operating Section (HP) (CFM) H † B P L<br />

<strong>REP</strong> 217-412 9420 17700 2520 (2) 20 136300 11’ 8-1/4” 7’ 3/4” 7’ 8-3/8” 11’ 11-3/4”<br />

<strong>REP</strong> 217-512 10060 18340 2550 (2) 15 122000 12’ 8-1/4” 8’ 3/4” 8’ 8-3/8” 11’ 11-3/4”<br />

<strong>REP</strong> 217-612 10140 18420 2550 (2) 20 133600 12’ 8-1/4” 8’ 3/4” 8’ 8-3/8” 11’ 11-3/4”<br />

<strong>REP</strong> 217-712 10920 19200 2940 (2) 20 131400 13’ 8-1/4” 9’ 3/4” 9’ 8-3/8” 11’ 11-3/4”<br />

<strong>REP</strong> 217-812 10180 18460 2550 (2) 25 143400 12’ 8-1/4” 8’ 3/4” 8’ 8-3/8” 11’ 11-3/4”<br />

<strong>REP</strong> 217-912 11000 19280 2940 (2) 30 149300 13’ 8-1/4” 9’ 3/4” 9’ 8-3/8” 11’ 11-3/4”<br />

Weights (LBS)<br />

Dimensions<br />

Fan<br />

Air<br />

Model Heaviest Motor Flow<br />

No. Shipping Operating Section (HP) (CFM) H † B P L<br />

<strong>REP</strong> 217-214 11580 20600 3180 (2) 15 137823 13’ 2-1/4” 8’ 6-3/4” 9’ 2-3/8” 13’ 11-3/4”<br />

<strong>REP</strong> 217-314 10880 19900 2770 (2) 25 164866 12’ 2-1/4” 7’ 6-3/4” 8’ 2-3/8” 13’ 11-3/4”<br />

<strong>REP</strong> 217-414 11660 20680 3180 (2) 20 150760 13’ 2-1/4” 8’ 6-3/4” 9’ 2-3/8” 13’ 11-3/4”<br />

<strong>REP</strong> 217-514 12560 21580 3630 (2) 20 148411 14’ 2-1/4” 9’ 6-3/4” 10’ 2-3/8” 13’ 11-3/4”<br />

<strong>REP</strong> 217-614 11700 20720 3180 (2) 25 161606 13’ 2-1/4” 8’ 6-3/4” 9’ 2-3/8” 13’ 11-3/4”<br />

<strong>REP</strong> 217-714 12600 21620 3630 (2) 25 158976 14’ 2-1/4” 9’ 6-3/4” 10’ 2-3/8” 13’ 11-3/4”<br />

<strong>REP</strong> 217-814 11740 20760 3180 (2) 30 171234 13’ 2-1/4” 8’ 6-3/4” 9’ 2-3/8” 13’ 11-3/4”<br />

<strong>REP</strong> 217-914 12640 21660 3630 (2) 30 168244 14’ 2-1/4” 9’ 6-3/4” 10’ 2-3/8” 13’ 11-3/4”<br />

Note: (1) An adequately sized bleed line must be installed in the cooling tower system to prevent build-up of impurities in the recirculated water.<br />

(2) Do not use catalog drawings for certified prints. Dimensions subject to change.<br />

(3) Connections larger than 3” are Beveled for Welding (BFW) and grooved for a mechanical coupling.<br />

(4) Adequate spacing must be allowed for access to the cooling tower.<br />

(5) Unit can operate as two (2) independent cells with the addition of a<br />

flume plate or water tight partition.<br />

† Height includes fan guard which ships factory mounted.<br />

4