THERMAL PERFORMANCE<br />

<strong>REP</strong> 224-018 to <strong>REP</strong> 224-918<br />

Temp<br />

Tower Capacity in USGPM at the Following Temperature Conditions (°F)<br />

EWT 90° 95° 90° 95° 95° 90° 95° 95° 95° 100°<br />

Model Motor LWT 80° 80° 80° 80° 85° 80° 80° 85° 85° 85°<br />

No. HP WB 68° 68° 70° 70° 70° 72° 72° 72° 75° 75°<br />

<strong>REP</strong> 224-018 (2) 25 3788 2886 3321 2543 4904 2847 2202 4528 3837 2955<br />

<strong>REP</strong> 224-118 (2) 30 3985 3045 3498 2692 5129 3005 2345 4742 4036 3118<br />

<strong>REP</strong> 224-218 (2) 25 4119 3226 3660 2884 5203 3186 2538 4833 4166 3298<br />

<strong>REP</strong> 224-318 (2) 40 4373 3371 3857 2993 5576 3328 2621 5169 4427 3449<br />

<strong>REP</strong> 224-418 (2) 30 4340 3415 3865 3059 5468 3375 2699 5082 4389 3488<br />

<strong>REP</strong> 224-518 (2) 30 4491 3604 4032 3275 5632 3566 2943 5235 4540 3674<br />

<strong>REP</strong> 224-618 (2) 40 4763 3776 4257 3397 5980 3734 3020 5559 4816 3855<br />

<strong>REP</strong> 224-718 (2) 50 5100 4066 4569 3667 6397 4020 3274 5946 5155 4148<br />

<strong>REP</strong> 224-818 (2) 50 5313 4271 4770 3885 6546 4226 3510 6194 5370 4351<br />

<strong>REP</strong> 224-918 (2) 60 5519 4436 4955 4037 * 4390 3648 6433 5578 4520<br />

Temp<br />

Tower Capacity in USGPM at the Following Temperature Conditions (°F)<br />

EWT 95° 100° 95° 97° 100° 102° 95° 96° 100° 102°<br />

Model Motor LWT 85° 85° 85° 87° 85° 85° 85° 86° 85° 85°<br />

No. HP WB 76° 76° 78° 78° 78° 78° 80° 80° 80° 80°<br />

<strong>REP</strong> 224-018 (2) 25 3596 2774 3070 3826 2387 2227 2445 2829 1919 1796<br />

<strong>REP</strong> 224-118 (2) 30 3786 2938 3241 4025 2536 2368 2587 2987 2059 1922<br />

<strong>REP</strong> 224-218 (2) 25 3930 3119 3412 4155 2724 2559 2777 3168 2251 2128<br />

<strong>REP</strong> 224-318 (2) 40 4164 3256 3579 4415 2826 2645 2884 3309 2309 2173<br />

<strong>REP</strong> 224-418 (2) 30 4148 3303 3609 4378 2897 2726 2953 3357 2402 2272<br />

<strong>REP</strong> 224-518 (2) 30 4303 3502 3787 4529 3123 2964 3174 3549 2665 2545<br />

<strong>REP</strong> 224-618 (2) 40 4557 3661 3984 4804 3228 3044 3286 3714 2698 2556<br />

<strong>REP</strong> 224-718 (2) 50 4884 3942 4282 5143 3486 3299 3546 3999 2936 2786<br />

<strong>REP</strong> 224-818 (2) 50 5090 4152 4484 5357 3714 3534 3771 4206 3195 3054<br />

AT 224-918 (2) 60 5287 4313 4658 5565 3860 3673 3919 4369 3325 3180<br />

*Flow exceeds maximum hydraulic limit.<br />

<strong>REP</strong> 224-720 to <strong>REP</strong> 224-920<br />

Temp<br />

Tower Capacity in USGPM at the Following Temperature Conditions (°F)<br />

EWT 90° 95° 90° 95° 95° 90° 95° 95° 95° 100°<br />

Model Motor LWT 80° 80° 80° 80° 85° 80° 80° 85° 85° 85°<br />

No. HP WB 68° 68° 70° 70° 70° 72° 72° 72° 75° 75°<br />

<strong>REP</strong> 224-720 (2) 40 4998 4012 4487 3646 6267 3970 3275 5826 5051 4089<br />

<strong>REP</strong> 224-820 (2) 50 5414 4350 4861 3956 6789 4304 3568 6311 5472 4434<br />

<strong>REP</strong> 224-920 (2) 60 5622 4518 5048 4108 7049 4471 3710 6553 5683 4604<br />

Temp<br />

Tower Capacity in USGPM at the Following Temperature Conditions (°F)<br />

EWT 95° 100° 95° 97° 100° 102° 95° 96° 100° 102°<br />

Model Motor LWT 85° 85° 85° 87° 85° 85° 85° 86° 85° 85°<br />

No. HP WB 76° 76° 78° 78° 78° 78° 80° 80° 80° 80°<br />

<strong>REP</strong> 224-720 (2) 40 4787 3893 4214 5039 3475 3303 3536 3950 2968 2837<br />

<strong>REP</strong> 224-820 (2) 50 5187 4222 4569 5459 3775 3596 3838 4284 3236 3097<br />

<strong>REP</strong> 224-920 (2) 60 5385 4393 4744 5669 3928 3736 3989 4450 3374 3224<br />

To Make a Selection: Locate the column with the desired operating temperature conditions. Read down the column until you find the GPM equal to or greater<br />

than the flow required. Read horizontally to the left to find the model number of the unit that will perform the duty.<br />

For selections and conditions other than those stated, consult your EVAPSPEC II Selection Program or local EVAPCO representative.<br />