THERMAL PERFORMANCE<br />

<strong>REP</strong> 217-111 to <strong>REP</strong> 217-911<br />

Temp<br />

Cooling Capacity in GPM<br />

EWT 90° 95° 90° 95° 95° 90° 95° 95° 95° 100°<br />

Model Motor LWT 80° 80° 80° 80° 85° 80° 80° 85° 85° 85°<br />

No. HP WB 68° 68° 70° 70° 70° 72° 72° 72° 75° 75°<br />

<strong>REP</strong> 217-111 (2) 7-1/2 1372 1032 1197 902 1798 1018 774 1653 1390 1058<br />

<strong>REP</strong> 217-211 (2) 7-1/2 1462 1127 1291 1000 1869 1112 875 1730 1480 1155<br />

<strong>REP</strong> 217-311 (2) 10 1589 1237 1408 1100 2018 1221 966 1872 1608 1265<br />

<strong>REP</strong> 217-411 (2) 15 1682 1287 1477 1139 2158 1270 995 1997 1703 1318<br />

<strong>REP</strong> 217-511 (2) 10 1684 1349 1510 1220 2112 1334 1094 1963 1702 1375<br />

<strong>REP</strong> 217-611 (2) 15 1830 1443 1632 1294 2304 1426 1146 2141 1851 1474<br />

<strong>REP</strong> 217-711 (2) 15 1913 1536 1718 1396 2400 1520 1256 2231 1934 1566<br />

<strong>REP</strong> 217-811 (2) 20 2037 1619 1823 1459 2556 1601 1300 2376 2059 1653<br />

<strong>REP</strong> 217-911 (2) 25 2233 1795 2005 1633 2700 1776 1476 2603 2257 1829<br />

Temp<br />

Cooling Capacity in GPM<br />

EWT 95° 100° 95° 97° 100° 102° 95° 96° 100° 102°<br />

Model Motor LWT 85° 85° 85° 87° 85° 85° 85° 86° 85° 85°<br />

No. HP WB 76° 76° 78° 78° 78° 78° 80° 80° 80° 80°<br />

<strong>REP</strong> 217-111 (2) 7-1/2 1300 992 1102 1386 847 782 865 1011 669 662<br />

<strong>REP</strong> 217-211 (2) 7-1/2 1393 1088 1199 1476 942 883 961 1106 771 727<br />

<strong>REP</strong> 217-311 (2) 10 1516 1196 1311 1604 1039 975 1059 1215 857 808<br />

<strong>REP</strong> 217-411 (2) 15 1597 1241 1369 1698 1073 1004 1095 1262 872 818<br />

<strong>REP</strong> 217-511 (2) 10 1612 1309 1418 1698 1163 1102 1182 1327 990 944<br />

<strong>REP</strong> 217-611 (2) 15 1749 1397 1525 1847 1227 1155 1249 1418 1020 964<br />

<strong>REP</strong> 217-711 (2) 15 1833 1493 1614 1929 1333 1265 1355 1513 1139 1087<br />

<strong>REP</strong> 217-811 (2) 20 1949 1570 1708 2054 1387 1310 1411 1593 1165 1103<br />

<strong>REP</strong> 217-911 (2) 25 2139 1745 1885 2252 1561 1486 1585 1768 1345 1285<br />

<strong>REP</strong> 217-412 to <strong>REP</strong> 217-912<br />

Temp<br />

Cooling Capacity in GPM<br />

EWT 90° 95° 90° 95° 95° 90° 95° 95° 95° 100°<br />

Model Motor LWT 80° 80° 80° 80° 85° 80° 80° 85° 85° 85°<br />

No. HP WB 68° 68° 70° 70° 70° 72° 72° 72° 75° 75°<br />

<strong>REP</strong> 217-412 (2) 20 1977 1522 1742 1350 2525 1502 1181 2340 2001 1577<br />

<strong>REP</strong> 217-512 (2) 15 1992 1566 1773 1403 2510 1548 1237 2332 2014 1601<br />

<strong>REP</strong> 217-612 (2) 20 2190 1736 1958 1562 2750 1717 1387 2557 2214 1773<br />

<strong>REP</strong> 217-712 (2) 20 2253 1810 2023 1646 2825 1792 1485 2626 2277 1845<br />

<strong>REP</strong> 217-812 (2) 25 2338 1864 2095 1680 2933 1843 1498 2726 2364 1902<br />

<strong>REP</strong> 217-912 (2) 30 2484 1997 2231 1817 * 1976 1642 2896 2510 2035<br />

Temp<br />

Cooling Capacity in GPM<br />

EWT 95° 100° 95° 97° 100° 102° 95° 96° 100° 102°<br />

Model Motor LWT 85° 85° 85° 87° 85° 85° 85° 86° 85° 85°<br />

No. HP WB 76° 76° 78° 78° 78° 78° 80° 80° 80° 80°<br />

<strong>REP</strong> 217-412 (2) 20 1882 1469 1615 1996 1273 1192 1299 1493 1038 978<br />

<strong>REP</strong> 217-512 (2) 15 1903 1515 1656 2009 1329 1250 1354 1539 1101 1042<br />

<strong>REP</strong> 217-612 (2) 20 2096 1680 1832 2209 1481 1400 1511 1708 1238 1175<br />

<strong>REP</strong> 217-712 (2) 20 2158 1759 1902 2272 1573 1495 1597 1783 1347 1287<br />

<strong>REP</strong> 217-812 (2) 25 2240 1804 1963 2358 1596 1512 1625 1833 1344 1275<br />

<strong>REP</strong> 217-912 (2) 30 2380 1941 2097 2505 1737 1653 1763 1967 1495 1429<br />

*Flow exceeds maximum hydraulic limit.<br />

<strong>REP</strong> 217-214 to <strong>REP</strong> 217-914<br />

Temp<br />

Cooling Capacity in GPM<br />

EWT 90° 95° 90° 95° 95° 90° 95° 95° 95° 100°<br />

Model Motor LWT 80° 80° 80° 80° 85° 80° 80° 85° 85° 85°<br />

No. HP WB 68° 68° 70° 70° 70° 72° 72° 72° 75° 75°<br />

<strong>REP</strong> 217-214 (2) 15 2201 1724 1955 1541 2781 1702 1355 2583 2227 1762<br />

<strong>REP</strong> 217-314 (2) 25 2381 1838 2102 1633 3030 1814 1432 2808 2411 1881<br />

<strong>REP</strong> 217-414 (2) 20 2420 1909 2158 1714 3042 1887 1520 2828 2446 1950<br />

<strong>REP</strong> 217-514 (2) 20 2492 2001 2238 1819 3126 1981 1637 2906 2520 2039<br />

<strong>REP</strong> 217-614 (2) 25 2618 2079 2341 1872 3284 2055 1666 3053 2646 2122<br />

<strong>REP</strong> 217-714 (2) 25 2703 2173 2426 1976 3419 2149 1784 3151 2732 2214<br />

<strong>REP</strong> 217-814 (2) 30 2768 2209 2480 1993 3472 2184 1780 3227 2798 2253<br />

<strong>REP</strong> 217-914 (2) 30 2856 2295 2564 2088 3507 2272 1887 3329 2886 2338<br />

Temp<br />

Cooling Capacity in GPM<br />

EWT 95° 100° 95° 97° 100° 102° 95° 96° 100° 102°<br />

Model Motor LWT 85° 85° 85° 87° 85° 85° 85° 86° 85° 85°<br />

No. HP WB 76° 76° 78° 78° 78° 78° 80° 80° 80° 80°<br />

<strong>REP</strong> 217-214 (2) 15 2100 1666 1823 2221 1455 1367 1484 1692 1201 1137<br />

<strong>REP</strong> 217-314 (2) 25 2268 1776 1952 2405 1544 1434 1573 1796 1263 1178<br />

<strong>REP</strong> 217-414 (2) 20 2313 1849 2017 2440 1626 1524 1655 1872 1353 1272<br />

<strong>REP</strong> 217-514 (2) 20 2387 1945 2102 2514 1738 1646 1765 1970 1484 1414<br />

<strong>REP</strong> 217-614 (2) 25 2504 2015 2193 2639 1780 1680 1810 2044 1492 1413<br />

<strong>REP</strong> 217-714 (2) 25 2589 2111 2281 2725 1887 1796 1917 2139 1620 1548<br />

<strong>REP</strong> 217-814 (2) 30 2651 2142 2326 2791 1895 1788 1928 2169 1597 1509<br />

<strong>REP</strong> 217-914 (2) 30 2735 2231 2410 2879 1996 1899 2027 2261 1718 1642<br />

To Make a Selection: Locate the column with the desired operating temperature conditions. Read down the column until you find the GPM<br />

equal to or greater than the flow required. Read horizontally to the left to find the model number of the unit that will perform the duty.<br />

For selections and conditions other than those stated, consult your EVAPSPEC II Selection Program or local EVAPCO representative.<br />

5