PBC Control Date: 1_03/22/10<br />

Project Rev: A_07/02/10<br />

sequence <strong>of</strong> installation, testing and inspecting procedures, and protection and<br />

repairs.<br />

E. Field Quality Assurance: Implement <strong>the</strong> ABAA Quality Assurance Program<br />

requirements. Cooperate with ABAA inspectors and independent testing and inspection<br />

agencies engaged by <strong>the</strong> Owner (if any). Do not permit covering <strong>of</strong> <strong>the</strong> air and vapor<br />

barrier membrane until it has been inspected, tested and accepted.<br />

F. Mock-Up: Build mock-up <strong>of</strong> barrier on exterior wall assembly where directed by<br />

Architect, minimum 10 ft. by 10ft.<br />

1. Coordinate construction <strong>of</strong> mockup to permit inspection and testing before<br />

external insulation and cladding is installed.<br />

2. If <strong>the</strong> Architect determines mockups do not comply with requirements,<br />

reconstruct mockups and apply barrier until mockups are approved.<br />

3. Remove mock-up when acceptable to <strong>the</strong> Architect.<br />

G. Mock-Up Tests for Air and Water Infiltration: Test mock-up at Contractor’s expense<br />

for air and water infiltration in accordance with ASTM E 1186 (air leakage location),<br />

ASTM E 783 (air leakage quantification), and ASTM E 1105 (water penetration). Use<br />

smoke tracer to locate sources <strong>of</strong> air leakage. If deficiencies are found, reconstruct<br />

mock-up and retest until satisfactory results are obtained. Deficiencies include air<br />

leakage beyond values specified, uncontrolled water leakage, unsatisfactory<br />

workmanship.<br />

1. Perform <strong>the</strong> air leakage tests and water penetration test <strong>of</strong> mock-up prior to<br />

installation <strong>of</strong> cladding and trim but after installation <strong>of</strong> all fasteners for cladding<br />

and trim and after installation <strong>of</strong> o<strong>the</strong>r penetrating elements having been flashed<br />

in.<br />

2. Perform additional tests as necessary to achieve specified performance criteria<br />

after initial testing.<br />

H. Mock-Up Tests for Membrane Adhesion: Test mock-up at Contractor’s expense <strong>of</strong><br />

membrane for adhesion at in accordance with ASTM D 4541 using a Type 1 pull tester<br />

except that <strong>the</strong> disk used shall be 100mm in diameter and <strong>the</strong> membrane shall be cut<br />

through to separate <strong>the</strong> material attached to <strong>the</strong> disk from <strong>the</strong> surrounding material.<br />

Perform test after curing period recommended by <strong>the</strong> manufacturer. Record mode <strong>of</strong><br />

failure and area which failed in accordance with ASTM D 4541.<br />

1. Modify products or procedures and retest until successful.<br />

1.6 DELIVERY, STORAGE, AND HANDLING<br />

A. Deliver materials to Project site in original packages with seals unbroken, labeled with<br />

manufacturer's name, product, date <strong>of</strong> manufacture, and directions for storage.<br />

B. Store materials in <strong>the</strong>ir original undamaged packages in a clean, dry, protected location<br />

and within temperature range required by air and vapor barrier membrane manufacturer.<br />

Protect stored materials from direct sunlight.<br />

C. Handle materials in accordance with manufacturer’s recommendations.<br />

CHICAGO POLICE DEPARTMENT<br />

12 TH DISTRICT POLICE STATION 07262-4 FLUID APPLIED AIR AND<br />

PBC-PROJECT# 09070<br />

VAPOR BARRIER