<strong>ASDA</strong>-<strong>B2</strong><br />

Chapter 2 Installation and Storage<br />

2.5 Circuit Interrupter and Fuse Current Recommended Value<br />

‣ Caution: Please use circuit interrupter and fuse which are recognized by and comply with<br />

the UL or CSA standards.<br />

Servo Drive Model Recommended Breaker Recommended Fuse (Class T)<br />

Operation Mode General General<br />

ASD-<strong>B2</strong>-0121-B 5A 5A<br />

ASD-<strong>B2</strong>-0221-B 5A 6A<br />

ASD-<strong>B2</strong>-0421-B 10A 10A<br />

ASD-<strong>B2</strong>-0721-B 10A 20A<br />

ASD-<strong>B2</strong>-1021-B 15A 25A<br />

ASD-<strong>B2</strong>-1521-B 20A 40A<br />

ASD-<strong>B2</strong>-2023-B 30A 50A<br />

ASD-<strong>B2</strong>-3023-B 30A 70A<br />

NOTE<br />

1) When using a GFCI (Ground Fault Circuit Interrupter), select a current sensor with sensitivity of<br />

equal to or more than 200mA, and not less than 0.1-second detection time to avoid nuisance<br />

tripping.<br />