6.3 Action at communication error<br />

USER MANUAL<br />

Revision 0.14<br />

2000-01-14<br />

In case of occurring transmission errors (communication cutoff with the master), the following actions can be selected.<br />

1) Select action when error is detected. (o27)<br />

o27 Action at error detection Remarks<br />

0 Immediate <strong>for</strong>ced stop Er5<br />

1 Continue operation within o28 time and stop Er5<br />

2 Continue operation according to the last command<br />

received until restoration of the communication. If the<br />

communication is not restored be<strong>for</strong>e the o28 time<br />

expires, then immediate <strong>for</strong>ced stop.<br />

3 Continue operation till restoration of the<br />

communication, and after the restoration, follow to<br />

designation of communication.<br />

2) Setting time of timer at error (o28)<br />

0.0 – 60.0s<br />

HMS FIELDBUS SYSTEMS AB 18<br />

Er5<br />

Automatic restoration<br />

after restoring<br />

communication<br />

In a case of o27=0 (Mode of immediate <strong>for</strong>ced stop at communication error detection)<br />

Command<br />

from Master<br />

Internal<br />

operation<br />

of inverter<br />

Communication<br />

state<br />

Display<br />

FWD<br />

Setting<br />

frequency<br />

Operation<br />

command<br />

Setting<br />

frequency<br />

Output<br />

frequency<br />

Normal<br />

Error<br />

Normal<br />

Normal Er 5<br />

ON<br />

Operation<br />

Communication failure<br />

ON<br />

Stop<br />

Coast-to-stop<br />

Continue operation<br />

using the command<br />

just be<strong>for</strong>e the error<br />

within o28 time, but<br />

when restoring,<br />

operate following to<br />

the designation of<br />

communication.<br />

Alarm reset<br />