7.6 Malfunction codes<br />

Inverter code (M16- (M1<br />

M19)<br />

Description Malfunction code<br />

(HEX)<br />

0 No alarm - 0000<br />

1 Overcurrent (During acceleration) OC1 2301<br />

2 Overcurrent (During deceleration) OC2 2302<br />

3 Overcurrent (While running at constant<br />

speed)<br />

OC3 2303<br />

4 Overcurrent (Input) OC 2100<br />

5 Ground fault EF 2330<br />

6 Overvoltage (During acceleration) OU1 3211<br />

7 Overvoltage (During deceleration) OU2 3212<br />

8 Overvoltage (While running at constant<br />

speed)<br />

OU3 3213<br />

10 Undervoltage LU 3220<br />

11 Input phase lose Lin 3130<br />

12 Power supply frequency abnormal FrE 3140<br />

13 AC Fuse blown ACF 5453<br />

14 DC Fuse blown FUS 5450<br />

16 DC link charge circuit abnormal PbF 5120<br />

17 Overheat of heat sink in inverter OH1 4310<br />

18 External alarm input OH2 9000<br />

19 Overheat of unit internal temp. OH3 4110<br />

20 Overheat of motor OH4 4300<br />

22 Overheat of DB resistance dbH 4210<br />

23 Electronic thermal overload relay (Motor<br />

1)<br />

24 Electronic thermal overload relay (Motor<br />

2)<br />

OL1 2211<br />

OL2 2212<br />

25 Electronic thermal overload relay (Inverter) OLU 2200<br />

27 Overspeed OS 7310<br />

28 PG error Pg 7301<br />

29 Thermistor circuit disconnection nrb 5000<br />

31 Memory error Er1 5500<br />

32 KEYPAD panel communication error Er2 7520<br />