7. Modbus process image in the memory of the<br />

<strong>COM462RTU</strong><br />

The device holds a process image in the memory. It represents the current statuses<br />

and values of up to 150 BMS devices for each monitored internal BMS bus.<br />

7.1 Requesting data<br />

7.1.1 Modbus function code<br />

The memory in the <strong>COM462RTU</strong> can be read using the Modbus function 0x03<br />

(read several registers). The size of the data volume to be queried depends on<br />

the number of bytes selected in the Modbus client being used. Up to 125<br />

Words (0x7D) can be read by one single request.<br />

An individual addressable byte, such as the set bit of a stored common alarm,<br />

can also be read out.<br />

7.1.2 How are memory areas organised<br />

Memory utilisation<br />

Start address<br />

End of the<br />

memory area<br />

Size of the<br />

memory area<br />

Reference values<br />

for testing purposes<br />

0x0000 0x00FF 0x0100<br />

Process image 0x0100 0x95FF 0x9500<br />

Unused 0x96FF 0xFFFF 0x6900<br />

In some Modbus clients, an offset of 1 must be added to<br />

the register addresses. Example: Process image start address<br />

= 0x0101.<br />

<strong>COM462RTU</strong>_D00010_00_M_XXEN/07.2013<br />