Modbus process image in the memory of the <strong>COM462RTU</strong><br />

7.3.3 Reference value on channel 2<br />

The following reference value is stored in this channel: 12.34 A<br />

Word 0x14 0x15 0x16 0x17<br />

HiByte LoByte HiByte LoByte HiByte LoByte HiByte LoByte<br />

0x41 0x45 0x70 0xA4 0x00 0x03 0x00 0x4A<br />

Floating point value (Float) AT&T R&U Description<br />

12,34 No/No Ampere Overcurrent<br />

Tab. 7.5: Reference data stored in channel 2<br />

7.3.4 Explanation of how to access floating point values<br />

The test value 12.34 can be read out via Modbus/RTU using Modbus function<br />

0x03 at the address 0x0014. The test value has a size of 2 words.<br />

Proceed as follows:<br />

1. Determine the correct byte offset<br />

Interpreting both words as unsigned integer values should result in the<br />

following values:<br />

Word 1 with address 0x14: unsigned integer value => 16709 (0x4145)<br />

Word 2 with address 0x15: unsigned integer value => 28836 (0x70A4)<br />

2. Determine the correct byte resp. word swap<br />

There are four different combinations of swapping. The only correct<br />

value is 12.34.<br />

All swapping combinations are represented in the following table.<br />

<strong>COM462RTU</strong>_D00010_00_M_XXEN/07.2013<br />