Modbus process image in the memory of the <strong>COM462RTU</strong><br />

7.2.6.3 R&U = Range and unit<br />

Bit 7 6 5 4 3 2 1 0 Meaning<br />

Unit<br />

x x x 0 0 0 0 0 Invalid (init)<br />

x x x 0 0 0 0 1 No unit<br />

x x x 0 0 0 1 0 Ω<br />

x x x 0 0 0 1 1 A<br />

x x x 0 0 1 0 0 V<br />

x x x 0 0 1 0 1 %<br />

x x x 0 0 1 1 0 Hz<br />

x x x 0 0 1 1 1 Baud<br />

x x x 0 1 0 0 0 F<br />

x x x 0 1 0 0 1 H<br />

x x x 0 1 0 1 0 °C<br />

x x x 0 1 0 1 1 °F<br />

x x x 0 1 1 0 0 Second<br />

x x x 0 1 1 0 1 Minute<br />

x x x 0 1 1 1 0 Hour<br />

x x x 0 1 1 1 1 Day<br />

x x x 1 0 0 0 0 Month<br />

x x x … … … … … Reserved<br />

x x x 1 1 1 1 0 CODE<br />

x x x 1 1 1 1 1 Reserved<br />

x x x … … … … … Reserved<br />

x x x 1 1 1 1 1 Reserved<br />

<strong>COM462RTU</strong>_D00010_00_M_XXEN/07.2013<br />

37