Technical leaflet<br />
Hot Gas Bypass Capacity Regulators, type CPCE/LG<br />
Introduction<br />
CPCE capacity regulators are used to adapt<br />
compressor capacity to actual evaporator load.<br />
They are installed in a bypass line between the<br />
high and low pressure sides of the refrigeration<br />
system and is designed for hot gas injection into<br />
the evaporator just after the expansion valve.<br />
Liquid-gas mixer type LG can be used at the point<br />
of injection to assure a proper mixture.<br />
Features<br />
Metric conversions<br />
1 psi = 0.07 bar<br />
5<br />
/ 9<br />
(t 1<br />
°F – 32) = t 2<br />
°C<br />
CPCE hot gas capacity valve<br />
Superior control accuracy<br />
Provides protection against too low an evaporator<br />
temperature<br />
Direct connection to system suction line<br />
For use with CFC, HCFC and HFC refrigerants<br />
LG liquid gas mixer<br />
LG provides homogenous mixture of liquid and<br />
hot gas refrigerant in the evaporator<br />
Can be used for hot gas defrosting or reverse<br />
cycle systems<br />
US listed, file SA7200<br />
approved<br />
Refrigerants:<br />
CFC, HCFC, HFC<br />
Regulation range<br />
n p e<br />
= 0 to 85 psig<br />
n Factory setting = 5.8 psig<br />
Maximum working pressure:<br />
n MWP = 310 psig<br />
Maximum test pressure:<br />
n p’ = 400 psig<br />
Maximum media temperature: 285°F<br />
Minimum media temperature: –40°F<br />
© Danfoss Inc. 01-07 (USCO)<br />
USCOC.PK.000.C1.22<br />