Technical leaflet<br />

Hot Gas Bypass Capacity Regulators, type CPCE/LG<br />

Introduction<br />

CPCE capacity regulators are used to adapt<br />

compressor capacity to actual evaporator load.<br />

They are installed in a bypass line between the<br />

high and low pressure sides of the refrigeration<br />

system and is designed for hot gas injection into<br />

the evaporator just after the expansion valve.<br />

Liquid-gas mixer type LG can be used at the point<br />

of injection to assure a proper mixture.<br />

Features<br />

Metric conversions<br />

1 psi = 0.07 bar<br />

5<br />

/ 9<br />

(t 1<br />

°F – 32) = t 2<br />

°C<br />

CPCE hot gas capacity valve<br />

Superior control accuracy<br />

Provides protection against too low an evaporator<br />

temperature<br />

Direct connection to system suction line<br />

For use with CFC, HCFC and HFC refrigerants<br />

LG liquid gas mixer<br />

LG provides homogenous mixture of liquid and<br />

hot gas refrigerant in the evaporator<br />

Can be used for hot gas defrosting or reverse<br />

cycle systems<br />

US listed, file SA7200<br />

approved<br />

Refrigerants:<br />

CFC, HCFC, HFC<br />

Regulation range<br />

n p e<br />

= 0 to 85 psig<br />

n Factory setting = 5.8 psig<br />

Maximum working pressure:<br />

n MWP = 310 psig<br />

Maximum test pressure:<br />

n p’ = 400 psig<br />

Maximum media temperature: 285°F<br />

Minimum media temperature: –40°F<br />

© Danfoss Inc. 01-07 (USCO)<br />