Technical leaflet<br />

Crankcase Pressure Regulators, type KVL<br />

Introduction<br />

KVL crankcase pressure regulators are used to<br />

protect the compressor motor against overload<br />

experienced during startup after long off periods<br />

or just after defrost periods.<br />

They are installed in the suction line of<br />

refrigeration systems.<br />

Features<br />

Metric conversions<br />

1 psi = 0.07 bar<br />

5<br />

/ 9<br />

(t 1<br />

°F – 32) = t 2<br />

°C<br />

1 ton = 3.5 kW<br />

Accurate, adjustable pressure regulation<br />

Wide capacity and operating range<br />

Pulsation damping design<br />

Stainless steel bellows<br />

Compact angle design for easy installation in any<br />

position<br />

"Hermetic" brazed construction<br />

Available with flare and ODF solder<br />

connections<br />

For use with CFC, HCFC and HFC<br />

refrigerants<br />

C US approved, file SA7200<br />

Regulation range<br />

n 3 to 85 psig<br />

n Factory setting = 29 psig<br />

Maximum working pressure<br />

n KVL 12 to 22: PS = 261 psig<br />

n KVL 28 to 35: PS = 261 psig<br />

Maximum test pressure<br />

n KVL 12 to 22: p' = 405 psig<br />

n KVL 28 to 35: p' = 370 psig<br />

Maximum temperature of medium: 266°F<br />

Minimum temperature of medium: –76°F<br />

Maximum P-band<br />

n KVL 12 to 22: 29 psi<br />

n KVL 28 to 35: 22 psi<br />

© Danfoss Inc. 01-07 (USCO)<br />