F.R.A.M.E.<br />
The central airport building was completely renewed and provided for a larger flow of<br />
passengers with more comfort and more services. The new fire safety concept addresses all<br />
weaknesses found during the analysis of the 1996 event, and uses the following main goals :<br />
minimising fire loads,<br />
compartimentation,<br />
early detection of fire,<br />
smoke control,<br />
safeguarding the evacuation<br />
The data available in the reference article were enough to recalculate the fire risk for the new<br />
concept. The results of this calculation show a very low residual risk, which goes beyond the<br />
standard "good" level proposed by <strong>FRAME</strong>. In the next table , the improved values are in bold.<br />
Item explanation (sub) factor Value Result<br />
Type of occupancy Dusseldorf Airport 2000+ concept<br />
<strong>Fire</strong> load immobile Qi 150<br />
<strong>Fire</strong> load mobile Qm 400 q=1.28<br />
Temperature rise T 250<br />
Average dimension m 0.3<br />
Reaction to fire M 1.0 i=0.90<br />
Length l 250<br />
Width b 90 g=3.61<br />
Level level access improved E 0 e=1.00<br />
Height of room h 5<br />
Ventilation smoke venting system k 1.16 % v=0.94<br />
Access direction Z 2<br />
Height difference H 0 z=1.00<br />
Potential <strong>Risk</strong>s P= 4.30 P1=1.19 P2=3.37<br />
Activation factor<br />
Main: non industrial a 0<br />
a=0.0<br />
Heating : ok<br />
Electrical: ok<br />
Explosion: no<br />
Secondary: none<br />
0<br />
0<br />
0<br />
0<br />
Occupants Number: 4000<br />
Mobility factor: 2<br />
Exits X 72<br />
Exit directions k 2<br />
Evacuation time factor<br />
t=0.37<br />
Content factor: 200 M. Euro c=0.37<br />
environment factor r r= 0.32<br />
dependency factor d d= 0.30<br />
Acceptable <strong>Risk</strong>s A= 0.86 A1= 0.91 A2 =0.93<br />
Water supplies adequate W=1.00<br />
Normal protection limited training N = 0.90<br />
Special Protection automatic detection,<br />
S= 14.64<br />
sprinklers, permanently<br />
staffed station, private<br />
airport brigade<br />
<strong>Fire</strong> resistance Structure: 90<br />
F=1.08<br />
Walls: 60<br />
Ceiling:60<br />
Partitions:0<br />
Escape protection see above U= 12.04<br />
Salvage<br />
safeguarded data and<br />
Y=1.63<br />
repair<br />
Calculated <strong>Risk</strong>s: R= 0.35 R1= 0.12 R2=0.17<br />
Conclusion:<br />
inadequate protection<br />
20