Installation<br />

Table 2-2, DC Wire Size For Increased Distance (in free air)<br />

Inverter<br />

Model<br />

Minimum Recommended DC Wire Size (one way)*<br />

1-3 feet 3-5 feet 5-10 feet<br />

<strong>RD</strong>2212 #4/0 AWG (107.16 mm 2 ) #4/0 AWG x2 (107.16 mm 2 ) not recommended<br />

<strong>RD</strong>1824 #2/0 AWG (67.4 mm 2 ) #2/0 AWG (67.4 mm 2 ) #4/0 AWG (107.16 mm 2 )<br />

<strong>RD</strong>2824 #4/0 AWG (107.16 mm 2 ) #4/0 AWG (107.16 mm 2 ) #4/0 AWG x2 (107.16 mm 2 )<br />

<strong>RD</strong>3924 #4/0 AWG (107.16 mm 2 ) #4/0 AWG x2 (107.16 mm 2 ) not recommended<br />

* Copper wire rated with 90°C (194°F) insulation at an ambient temperature of 30°C (86°F).<br />

2.4.3 DC Cable Connections<br />

Do not put anything between the DC cable ring lug and the battery terminal post or the flat metal<br />

part of the inverter’s DC terminal. When connecting the DC cable to the battery or inverter DC<br />

terminals, the cable should be placed directly against the inverter or battery terminals. Incorrectly<br />

installed hardware causes a high resistance connection, which could lead to poor inverter/charger<br />

performance and may melt the cable and terminal connections.<br />

Follow the examples in Figures 2-5 and 2-6 to connect the DC cables and stack the hardware<br />

correctly. Tighten the terminal connections from 10 to 12 ft lbf (13.6 to 16.3 N-m).<br />

CAUTION: The DC terminal and Kep nuts are made of stainless steel, which has a high<br />

likelihood of seizure. To help prevent the bolt and nut from seizing — causing the bolts<br />

to strip or snap/break-off — the use of anti-seize lubricant is highly recommended.<br />

Info: If antioxidant grease or spray is used, apply it after all the connections have been<br />

made and are properly tightened.<br />

Info: A 1/2-inch wrench or socket is used to tighten the 5/16 SAE Kep nuts.<br />

nut<br />

split<br />

washer<br />

flat<br />

washer<br />

Battery<br />

Temperature<br />

Sensor<br />

CAUTION:<br />

Ensure nothing is<br />

placed between<br />

the DC terminal<br />

and the ring lug.<br />

battery cable<br />

(with ring lug)<br />

CAUTION:<br />

Ensure nothing is<br />

placed between<br />

the cable ring lug<br />

and the battery<br />

post.<br />

battery<br />

post<br />

Inverter DC<br />

terminal<br />

(5/16 -18" bolt,<br />

5/8" length)<br />

battery cable<br />

(with ring lug)<br />

5/16 -18"<br />

Flange or<br />

Kep nut<br />

Figure 2-5, Battery Hardware<br />

Installation<br />

© 2010 <strong>Magnum</strong> <strong>Energy</strong>, Inc.<br />

Figure 2-6, Inverter DC Hardware<br />

Installation<br />

Page 16