Operation<br />
3.8 Factory Default Values<br />
Your <strong>RD</strong> <strong>Series</strong> inverter/charger uses default values for the adjustable settings (see Table 3-2) that<br />
are adequate for most installations. If some of your operating parameters need to be changed from<br />
the default values, the optional ME-RC50 remote control can be used to make those changes. To<br />
help you determine if you need the ME-RC50 remote display, information on the inverter/charger<br />
settings that can be changed is provided below. The settings, once programmed, are saved in the<br />
remote’s non-volatile memory and are preserved until changed – even if DC power to the inverter<br />
is lost (as long as the ME-RC50 remote is connected). For information on the full range of settings<br />
for each function, refer to the ME-RC50 Owner’s <strong>Manual</strong> at www.magnumenergy.com.<br />
• Shore: This setting ensures the inverter AC loads receive the maximum current available<br />
from the utility power or generator. When the total current used to power the AC loads<br />
and to charge the batteries begins to approach the “Shore” setting, the current that was<br />
used for charging the batteries will automatically be reduced.<br />
• 01 Search Watts: This setting allows you to turn off the power-saving Search Mode circuitry<br />
or adjust the power level at which the inverter will “wake up” and start inverting.<br />
• 02 LowBattCutOut: This setting determines when the inverter will turn off based on<br />
low battery voltage. The inverter turns off automatically after the battery voltage has<br />
been below this setting for more than one minute. This protects the batteries from overdischarge<br />
and the AC loads from unregulated power (brown-outs).<br />
• 03 Batt AmpHrs: This setting allows the user to input the battery bank size in amp hours,<br />
which tells the charger how long to charge the batteries in the Absorb Charge stage.<br />
• 04 Battery Type: Sets the type of batteries being used in the system; this information<br />
tells the charger what voltage level to use to charge the batteries.<br />
• 05 Charge Rate: This setting can be used to turn off the charger, limit the amount of<br />
current that the charger can use (leaving more current available to power loads); or, to<br />
ensure small battery banks are not overheated because of a too high charge rate.<br />
• 06 VAC Dropout: Sets the minimum AC voltage that must be present on the AC input<br />
before the unit transfers from Standby Mode to Inverter Mode. This protects the AC loads<br />
from utility power outages and brown-outs.<br />
Using the ME-RC50 remote also provides the following features:<br />
•<br />
•<br />
•<br />
allows you to enable an equalize charge for certain battery types<br />
displays inverter/charger’s operating status<br />
provides fault information for troubleshooting<br />
Table 3-2, Inverter/Charger Default Values<br />
Adjustable Settings Default Values<br />
Shore<br />
30 amps<br />
01 Search Watts 5 watts<br />
02 LowBattCutOut 10 VDC (12-volt models), 20 VDC (24-volt models)<br />
03 Batt AmpHrs 600 Amp Hours (Absorb Time = 120 minutes)<br />
04 Battery Type Flooded - Liquid Lead Acid<br />
05 Charge Rate 100%<br />
06 VAC Dropout 80 VAC<br />