3. General Specifications (Environment Conditions)<br />

3.3 Heat Radiation Countermeasures<br />

The following shows an example of calculation applied to heat radiation countermeasures for the operation<br />

panel. Because heat will accumulate in the upper portions of the unit, install an agitating fan as required.<br />

Display unit<br />

200<br />

(Agitating fan)<br />

500<br />

260 140<br />

120<br />

600<br />

<br />

(1) Calculation of unit heating value<br />

Heating value (W)<br />

Total heating value of units (W):<br />

28W (= control unit + display unit + keyboard unit + operation panel I/O unit)<br />

Total heating value (W) by machine input (D1):<br />

5.6W (= 24V; total heating value when the 32 points are simultaneously turned ON × 7.3mA × 32)<br />

... 24V; current consumption per point of the operation panel I/O unit DI ÷ 3.3kΩ ≒ 7.3mA<br />

Total heating value W = 33.6W (28 + 5.6)<br />