CHAPTER 1 -<br />

INSTALLATION<br />

1.1 Inspection<br />

• Inspect the inverter for any damage that may have occurred during shipping.<br />

• Check the nameplate on the inverter. Verify the inverter unit is the correct one for the application. The numbering<br />

system for the inverter is as shown below.<br />

SV 008 <strong>iS5</strong> 2 XXX U<br />

(480)<br />

LG Inverter Motor Capacity Series Name Input Voltage<br />

008: 1 HP 075: 10 HP 2: 200 ~ 230V (10%) (50/60Hz)<br />

015: 2 HP 110: 15 HP 4: 380 ~ 460V (10%) (50/60Hz) UL Listed<br />

022: 3 HP 150: 20 HP 4: 380 ~ 480V(10%) (50/60Hz)<br />

037: 5 HP 185: 25 HP<br />

055: 7.5 HP 220: 30 HP N: Without Keypad<br />

O/E: UL Open/Enclosed Type 1<br />

DB: Built-in DB Unit<br />

1.2 Environmental Conditions<br />

• Verify ambient condition for the mounting location.<br />

- Ambient temperature should not be below 14ºF (-10ºC) or exceed 104ºF (40ºC).<br />

- Relative humidity should be less than 90% (non-condensing).<br />

- Altitude should be below 3,300ft (1,000m).<br />

• Do not mount the inverter in direct sunlight and isolate it from excessive vibration.<br />

• If the inverter is going to be installed in an environment with high probability of penetration of dust, it must be<br />

located inside watertight electrical boxes, in order to get the suitable IP degree.<br />

1.3 Mounting<br />

…<br />

• The inverter must be mounted vertically with sufficient horizontal and vertical space between adjacent equipment<br />

(A= Over 100mm, B= Over 50mm). However, A= Over 500mm and B= 200mm should be obtained for<br />

inverters with 40Hp and above.<br />

A<br />

<br />

<br />

<br />

<br />

<br />

<br />

B<br />

B<br />

A<br />

6