Chapter 1 – Installation<br />

1.8.1 Wiring Control Terminals<br />

• Wiring Precautions<br />

• CM and 5G terminals are insulated to each other. Do not connect these terminals with each other and do not<br />

connect these terminals to the power ground. Terminal 5G is indicated as CM from 30kW inverters and has the<br />

same potential as CM (Sequence Common Terminal).<br />

• Use shielded wires or twisted wires for control circuit wiring, and separate these wires from the main power circuits<br />

and other high voltage circuits.<br />

• It is recommended to use the cables of 1.25 mm(22 AWG) for connection to the control circuit terminals.<br />

• Control Circuit Terminal<br />

• The control input terminal of the control circuit is ON when the circuit is configured to the current flows out of the<br />

terminal, as shown in the following illustration. CM terminal is the common terminal for the contact input signals.<br />

Resistor<br />

Current<br />

FX<br />

24 VDC<br />

Resistor<br />

RX<br />

CM<br />

External Sequence<br />

Inverter Circuitry<br />

<br />

Do not apply voltage to any control input terminals (FX, RX, P1, P2, P3, JOG, BX, RST, CM).<br />

20