Chapter 2 - Operation<br />
Operation<br />
Analog Voltage Input (V1) + Operation via Terminal (FX/RX)<br />
Example (2)<br />
[Operation condition]<br />
-. Control mode: V/F control<br />
-. Reference Frequency: 50[Hz] analog input via V1 (Potentiometer)<br />
-. Accel/Decel time: Accel – 10 [Sec], Decel – 20 [Sec]<br />
-. Drive mode: Run/Stop via FX/RX terminal<br />
[Wiring]<br />
3P<br />
AC<br />
input<br />
R<br />
S<br />
T<br />
G<br />
B1<br />
B2<br />
U<br />
V<br />
W<br />
IM<br />
S/W<br />
Potentiometer<br />
1[kohm],1/2W<br />
FX<br />
RX<br />
BX<br />
RST<br />
JOG<br />
P1<br />
P2<br />
P3<br />
CM<br />
VR<br />
V1<br />
5G<br />
FM<br />
5G<br />
30A<br />
30C<br />
30B<br />
AXA<br />
AXC<br />
Step Parameter setting Code Description<br />
1 Control Mode Selection FU2-39 Set it to 0 {V/F}.<br />
2 Drive Mode DRV-3 Set it to 1 Fx/Rx-1.<br />
3 Frequency Mode DRV-4 Set it to 2 V1 Analog input.<br />
4<br />
50[Hz] freq command<br />
setting<br />
5 Accel/Decel time<br />
6 Terminal FX<br />
7 Terminal RX<br />
DRV-0<br />
DRV-2<br />
DRV-3<br />
Set freq command 50[Hz] via V1(potentiometer).<br />
Set Accel time to 10 [Sec] in DRV-2.<br />
Set Decel time to 20 [Sec] in DRV-3.<br />
Motor starts to rotate in Forward direction at 50Hz with Accel time<br />
10 [sec] when FX terminal is turned ON.<br />
Motor decelerates to stop with Decel time 20[sec] when FX<br />
terminal is turned OFF.<br />
When RX terminal is turned ON motor starts to rotate in Reverse<br />
direction at 50[Hz] with Accel time 10 [Hz]. When it is OFF, motor<br />
decelerates to stop with Decel time 20 [Sec].<br />