Chapter 3 – Function Settings<br />

FU2-40<br />

No<br />

All<br />

Rs+Lsigma<br />

Enc Test<br />

Tr<br />

Motor constants calculation disabled.<br />

Description<br />

All constants can be measured in this code but different constants are tuned<br />

according to control mode;<br />

For V/F, Slip compen, Sensorless_S, Sensorless_T:<br />

(No-load current, stator resistance, leakage inductance, stator inductance<br />

available)<br />

Note: Only no-load current can be calculated during V/F and Slip<br />

compensation.<br />

For Vector_SPD, Vector_T:<br />

(No-load current, stator resistance, leakage inductance, stator inductance,<br />

encoder test, rotor filter time constant)<br />

Calculates stator resistance, leakage inductance.<br />

Calculates the encoder status.<br />

Calculates Rotor filter time constant.<br />

6) Sensorless vector control<br />

Set FU2-39 to 2 {Sensorless_S} or 3 {Sensorless_T} to enable Sensorless vector control. It is strongly recommended<br />

to perform Auto-tuning for Sensorless before starting Sensorless control in order to maximize performance. Two types<br />

of Sensorless vector control are available; Sensorless_S or Sensorless_T.<br />

Parameter Name Code Description<br />

Control mode selection FU2-39 Select Sensorless_S or Sensorless_T.<br />

P, I gain for<br />

sensorless control<br />

FU2-45, FU2-46<br />

Set gain for Sensorless_S control.<br />

Starting freq FU1-22 Starting freq of the motor<br />

7) Vector control<br />

Set FU2-39 to 4 {Vector_SPD} or 5 {Vector_TRQ} to enable Vector control. Encoder should be installed to the motor<br />

with Sub-B board in the inverter to start this control.<br />

Parameter Name Code Description<br />

Usage of Pulse<br />

Input Signal<br />

Pulse Input Signal<br />

Selection<br />

EXT -12<br />

EXT -15<br />

Defines the method of pulse input with SUB-B board<br />

mounted. Vector control setting is valid only after this<br />

parameter is set to 1 {Feed-back}.<br />

3 types of pulse input: (A+B), A, -(A+B)<br />

Encoder Pulse Number EXT -16 Enters the pulse number of encoder in the motor.<br />

Before selecting Vector control mode, encoder setting should be done as indicated above. If the parameter value of<br />

actual motor is set in common setting, execute Auto-tuning before selecting vector control mode.<br />

40