Securing the Unit<br />
¡ Locations to secure the bolts.<br />
¡ Use M10-M12 for the retaining bolts.<br />
¡ Secure it firmiy so the unit will not fall during earthquakes and from sudden gusts of wind.<br />
Drainage<br />
¡ There are 3 holes in the bottom panel of<br />
the outdoor unit to drain condensation.<br />
Removing the Outer Panel<br />
2 Top panel<br />
1 Service panel<br />
1 Service panel<br />
¡Remove the screws, and pull the panel toward the direction.<br />
2 Top panel<br />
¡Remove the panel when cheking the abnormal indicator LED<br />
during the protective function.<br />
<strong>4.</strong>5.4 Setting for current limit SW (for SCM68YA, cooling only type)<br />
This unit has a current limit default velue of Max.Amp (17.5A) to change<br />
the default value, remove the front panel and set the switch fot the printed<br />
circit board etc., according to the following instructions.<br />
1 Changing the current limit to 11A.<br />
Turn on the SW6 shown in the figure.<br />
2 Changing the current limit to 8.5A.<br />
Turn on the SW5 and SW6 shown in the figure.<br />
CURRENT LIMIT SW<br />
SW5<br />
SW6<br />
11A<br />
SW5<br />
SW6<br />
8.5A<br />
SW5<br />
SW6<br />
ON<br />
OFF<br />
MAX.AMP.<br />
154