PREMIUM G SERIES INSTALLATION MANUAL<br />

Auxiliary Heat Ratings<br />

Model<br />

kW<br />

Btu/h<br />

Model Size Compatibility<br />

Stages<br />

Min cfm<br />

208V 230V 208V 230V 012 018 022 026 - 030 036 - 042 048 - 072<br />

EAS(H)4 2.9 3.8 1 9,700 12,900 250 •<br />

EAM(H)5 3.6 4.8 1 12,300 16,300 450 • • •<br />

EAM(H)8 5.7 7.6 2 19,400 25,900 550 • • •<br />

EAM(H)10 7.2 9.6 2 24,600 32,700 650 •<br />

EAL(H)10 7.2 9.6 2 24,600 32,700 1100 • •<br />

EAL(H)15 10.8 14.4 3 36,900 49,100 1250 • •<br />

EAL(H)20 14.4 19.2 4 49,200 65,500 1500 •<br />

Order the “H” part number when installed on horizontal and vertical rear discharge units<br />

5/8/12<br />

Air flow level for auxiliary heat (Aux) must be above the minimum cfm in this table<br />

Auxiliary Heat Electrical Data<br />

Model<br />

Supply<br />

Circuit<br />

Heater Amps Min Circuit Amp Fuse (USA) Fuse (CAN) CKT BRK<br />

208 V 240 V 208 V 240 V 208 V 240 V 208 V 240 V 208 V 240 V<br />

EAS(H)4 Single 13.7 15.8 17.9 20.5 20 20 20 20 20 20<br />

EAM(H)5 Single 17.3 20.0 26.7 30.0 30 30 30 30 30 30<br />

EAM(H)8 Single 27.5 31.7 39.3 44.6 40 45 40 45 40 45<br />

EAM(H)10 Single 34.7 40.0 48.3 55.0 50 60 50 60 50 60<br />

EAL(H)10 Single 34.7 40.0 53.3 60.0 60 60 60 60 60 60<br />

EAL(H)15<br />

EAL(H)20<br />

Single 52.0 60.0 75.0 85.0 80 90 80 90 70 100<br />

L1/L2 34.7 40.0 53.3 60.0 60 60 60 60 60 60<br />

L3/L4 17.3 20.0 21.7 25.0 25 25 25 25 20 30<br />

Single 69.3 80.0 96.7 110.0 100 110 100 110 100 100<br />

L1/L2 34.7 40.0 53.3 60.0 60 60 60 60 60 60<br />

L3/L4 34.7 40.0 43.3 50.0 45 50 45 50 40 50<br />

All heaters rated single phase 60 cycle and include unit blower load<br />

2/11/12<br />

All fuses type “D” time delay (or HACR circuit breaker in USA)<br />

Supply wire size to be determined by local codes<br />

16