PREMIUM G SERIES INSTALLATION MANUAL<br />

Microprocessor Control System cont.<br />

Freeze Sensing (Water Flow)<br />

This lockout mode occurs when the freeze thermistor<br />

temperature is at or below the selected freeze sensing point (well<br />

30°F or loop 15°F) for 30 continuous seconds.<br />

Condensate Overflow<br />

This lockout mode occurs when the condensate overfl ow level has<br />

been reached for 30 continuous seconds.<br />

Fan RPM<br />

The control board monitors fan RPM to sense operation. This<br />

lockout mode occurs if the fan RPM falls below the low RPM limit<br />

(100 RPM) for 30 continuous seconds.<br />

Thermostat Displays<br />

Fault Flash<br />

When using a TA32W02 or TP32W03 thermostat and SW2-8<br />

is in the pulsing “L” position, FaultFlash will enable a user to<br />

view the thermostat and count the fault indicator fl ashes to<br />

determine the lockout condition the unit is experiencing.<br />

FaultFlash Thermostats<br />

TA32W02 and TP32W03 Thermostats<br />

Thermostat Display<br />

Lockout Code<br />

Lockout Description<br />

2 Flashes High Pressure Fault<br />

3 Flashes Low Pressure Fault<br />

4 Flashes Not Applicable<br />

5 Flashes Water Flow Fault<br />

6 Flashes Not Applicable<br />

7 Flashes Condensate Fault<br />

8 Flashes Voltage out of Range<br />

9 Flashes RPM Fault<br />

32