PREMIUM G SERIES INSTALLATION MANUAL<br />
Microprocessor Control System cont.<br />
Freeze Sensing (Water Flow)<br />
This lockout mode occurs when the freeze thermistor<br />
temperature is at or below the selected freeze sensing point (well<br />
30°F or loop 15°F) for 30 continuous seconds.<br />
Condensate Overflow<br />
This lockout mode occurs when the condensate overfl ow level has<br />
been reached for 30 continuous seconds.<br />
Fan RPM<br />
The control board monitors fan RPM to sense operation. This<br />
lockout mode occurs if the fan RPM falls below the low RPM limit<br />
(100 RPM) for 30 continuous seconds.<br />
Thermostat Displays<br />
Fault Flash<br />
When using a TA32W02 or TP32W03 thermostat and SW2-8<br />
is in the pulsing “L” position, FaultFlash will enable a user to<br />
view the thermostat and count the fault indicator fl ashes to<br />
determine the lockout condition the unit is experiencing.<br />
FaultFlash Thermostats<br />
TA32W02 and TP32W03 Thermostats<br />
Thermostat Display<br />
Lockout Code<br />
Lockout Description<br />
2 Flashes High Pressure Fault<br />
3 Flashes Low Pressure Fault<br />
4 Flashes Not Applicable<br />
5 Flashes Water Flow Fault<br />
6 Flashes Not Applicable<br />
7 Flashes Condensate Fault<br />
8 Flashes Voltage out of Range<br />
9 Flashes RPM Fault<br />