PREMIUM G SERIES INSTALLATION MANUAL<br />

Single Speed/Dual Capacity Startup/Troubleshooting Form<br />

1. Job Information<br />

Model # Job Name: Loop: Open / Closed<br />

Serial # <strong>Install</strong> Date: Hot Water Generator: Y / N<br />

2. Flow Rate in gpm SOURCE COAX LOAD COAX (Water-to-Water)<br />

HEATING COOLING HEATING COOLING<br />

WATER IN Pressure: a. psi a. psi a. psi a. psi<br />

WATER OUT Pressure: b. psi b. psi b. psi b. psi<br />

Pressure Drop: a - b c. psi c. psi c. psi c. psi<br />

Look up flow rate in table: d. gpm d. gpm d. gpm d. gpm<br />

3. Temp. Rise/Drop Across Coaxial Heat Exchanger 1<br />

HEATING<br />

COOLING<br />

WATER IN Pressure: e. °F e. °F<br />

WATER OUT Pressure: f. °F f. °F<br />

Temperature Difference: g. °F g. °F<br />

4. Temp. Rise/Drop Across Air Coil SOURCE COAX LOAD COAX (Water-to-Water)<br />

HEATING COOLING HEATING COOLING<br />

SUPPLY AIR Temperature: h. °F h. °F h. °F h. °F<br />

RETURN AIR Temperature: i. °F i. °F i. °F i. °F<br />

Temperature Difference: j. °F j. °F j. °F j. °F<br />

5. Heat of Rejection (HR)/Heat of Extraction (HE)<br />

Brine Factor 2 : k.<br />

HEATING<br />

COOLING<br />

HR/HE = d x g x k l. Btu/h l. Btu/h<br />

STEPS 6-9 NEED ONLY BE COMPLETED IF A PROBLEM IS SUSPECTED.<br />

6. Watts ENERGY MONITOR<br />

HEATING<br />

COOLING<br />

Volts: m. Volts m. Volts<br />

Total Amps (Comp. + Blower) 3 : n. Amps n. Amps<br />

Watts = m x n x 0.85: o. Watts o. Watts<br />

7. Capacity<br />

HEATING<br />

COOLING<br />

Cooling Capacity = l - (o x 3.413):<br />

p. Btu/h p. Btu/h<br />

Heating Capacity = l + (o x 3.413):<br />

8. Efficiency<br />

HEATING<br />

COOLING<br />

Cooling EER = p / o:<br />

Heating COP = p / (o x 3.413):<br />

q. Btu/h q. Btu/h<br />

9. Superheat (S.H.)/Subcooling (S.C.)<br />

Software Version<br />

HEATING<br />

COOLING<br />

ABC:<br />

Suction Pressure: r. psi r. psi<br />

AXB:<br />

Suction Saturation Temperature: s. °F s. °F<br />

IZ2:<br />

Suction Line Temperature: t. °F t. °F<br />

T’STAT:<br />

S.H. = t - s u. °F u. °F<br />

Head Pressure: v. psi v. psi<br />

High Pressure Saturation Temp: w. °F w. °F<br />

Liquid Line Temperature 4 : x. °F x. °F<br />

S.C. = w - x y. °F y. °F<br />

NOTES:<br />

1 Steps 3-9 should be conducted with the hot water generator disconnected.<br />

2<br />

Use 500 for pure water, 485 for methanol or Environol. (This constant is derived by multiplying the weight of one gallon of water (8.34) times the minutes<br />

in one hour (60) times the specific heat of the fluid. Water has a specific heat of 1.0.<br />

3<br />

If there is only one source of power for the compressor and blower, amp draw can be measured at the source wiring connection.<br />

4<br />

Liquid line is between the coax and the expansion device in the cooling mode; between the air coil and the expansion device in the heating mode.<br />

51