PREMIUM G SERIES INSTALLATION MANUAL<br />
Single Speed/Dual Capacity Startup/Troubleshooting Form<br />
1. Job Information<br />
Model # Job Name: Loop: Open / Closed<br />
Serial # <strong>Install</strong> Date: Hot Water Generator: Y / N<br />
2. Flow Rate in gpm SOURCE COAX LOAD COAX (Water-to-Water)<br />
HEATING COOLING HEATING COOLING<br />
WATER IN Pressure: a. psi a. psi a. psi a. psi<br />
WATER OUT Pressure: b. psi b. psi b. psi b. psi<br />
Pressure Drop: a - b c. psi c. psi c. psi c. psi<br />
Look up flow rate in table: d. gpm d. gpm d. gpm d. gpm<br />
3. Temp. Rise/Drop Across Coaxial Heat Exchanger 1<br />
HEATING<br />
COOLING<br />
WATER IN Pressure: e. °F e. °F<br />
WATER OUT Pressure: f. °F f. °F<br />
Temperature Difference: g. °F g. °F<br />
4. Temp. Rise/Drop Across Air Coil SOURCE COAX LOAD COAX (Water-to-Water)<br />
HEATING COOLING HEATING COOLING<br />
SUPPLY AIR Temperature: h. °F h. °F h. °F h. °F<br />
RETURN AIR Temperature: i. °F i. °F i. °F i. °F<br />
Temperature Difference: j. °F j. °F j. °F j. °F<br />
5. Heat of Rejection (HR)/Heat of Extraction (HE)<br />
Brine Factor 2 : k.<br />
HEATING<br />
COOLING<br />
HR/HE = d x g x k l. Btu/h l. Btu/h<br />
STEPS 6-9 NEED ONLY BE COMPLETED IF A PROBLEM IS SUSPECTED.<br />
6. Watts ENERGY MONITOR<br />
HEATING<br />
COOLING<br />
Volts: m. Volts m. Volts<br />
Total Amps (Comp. + Blower) 3 : n. Amps n. Amps<br />
Watts = m x n x 0.85: o. Watts o. Watts<br />
7. Capacity<br />
HEATING<br />
COOLING<br />
Cooling Capacity = l - (o x 3.413):<br />
p. Btu/h p. Btu/h<br />
Heating Capacity = l + (o x 3.413):<br />
8. Efficiency<br />
HEATING<br />
COOLING<br />
Cooling EER = p / o:<br />
Heating COP = p / (o x 3.413):<br />
q. Btu/h q. Btu/h<br />
9. Superheat (S.H.)/Subcooling (S.C.)<br />
Software Version<br />
HEATING<br />
COOLING<br />
ABC:<br />
Suction Pressure: r. psi r. psi<br />
AXB:<br />
Suction Saturation Temperature: s. °F s. °F<br />
IZ2:<br />
Suction Line Temperature: t. °F t. °F<br />
T’STAT:<br />
S.H. = t - s u. °F u. °F<br />
Head Pressure: v. psi v. psi<br />
High Pressure Saturation Temp: w. °F w. °F<br />
Liquid Line Temperature 4 : x. °F x. °F<br />
S.C. = w - x y. °F y. °F<br />
NOTES:<br />
1 Steps 3-9 should be conducted with the hot water generator disconnected.<br />
2<br />
Use 500 for pure water, 485 for methanol or Environol. (This constant is derived by multiplying the weight of one gallon of water (8.34) times the minutes<br />
in one hour (60) times the specific heat of the fluid. Water has a specific heat of 1.0.<br />
3<br />
If there is only one source of power for the compressor and blower, amp draw can be measured at the source wiring connection.<br />
4<br />
Liquid line is between the coax and the expansion device in the cooling mode; between the air coil and the expansion device in the heating mode.<br />
51