PREMIUM G SERIES INSTALLATION MANUAL<br />

Blower Performance Data<br />

Single Speed Unit with Variable Speed ECM Motor<br />

MODEL<br />

MAX<br />

AIR FLOW DIP SWITCH SETTINGS<br />

ESP 1 2 3 4 5 6 7 8 9 10 11 12<br />

022<br />

030<br />

036<br />

0.50<br />

0.50<br />

0.50<br />

400<br />

400<br />

650<br />

500<br />

500<br />

750<br />

600<br />

600<br />

850<br />

700<br />

700<br />

1000<br />

800<br />

800<br />

1100<br />

900<br />

900<br />

1200<br />

1000<br />

1000<br />

1300<br />

1100<br />

1100<br />

1400<br />

1200<br />

1200<br />

1500<br />

L<br />

L<br />

M<br />

L<br />

M<br />

H<br />

M<br />

H<br />

H<br />

036 800 1000 1100 1300 1500 1600 1800<br />

0.75<br />

w/1hp* L M H<br />

042 0.50<br />

650 800 900 1050 1150 1250 1350 1450 1550<br />

L M H<br />

042 800 900 1000 1200 1400 1600 1700 1850 2000 2200 2300 2400<br />

0.75<br />

w/1hp* L M H<br />

048 0.50<br />

650 800 900 1050 1150 1250 1350 1450 1550<br />

L M H<br />

048 800 900 1000 1200 1400 1600 1700 1850 2000 2200 2300 2400<br />

0.75<br />

w/1hp* L M H<br />

060<br />

070<br />

0.75<br />

0.75<br />

800<br />

800<br />

950<br />

950<br />

1100<br />

1100<br />

1300<br />

1300<br />

1500<br />

1500<br />

1750<br />

1750<br />

1950<br />

1950<br />

2100<br />

2100<br />

2300<br />

2300<br />

L<br />

L<br />

M<br />

M<br />

H<br />

H<br />

Factory settings are at recommended L-M-H DIP switch locations<br />

M-H settings MUST be located within boldface CFM range<br />

Lowest and Highest DIP switch settings are assumed to be L and H respectively<br />

Dual Capacity Unit with Variable Speed ECM Motor<br />

CFM is controlled within ±5% up to the maximum ESP<br />

Max ESP includes allowance for wet coil and standard filter<br />

MODEL<br />

MAX<br />

AIR FLOW DIP SWITCH SETTINGS<br />

ESP 1 2 3 4 5 6 7 8 9 10 11 12<br />

026<br />

038<br />

0.50<br />

0.50<br />

400<br />

650<br />

500<br />

750<br />

600<br />

850<br />

700<br />

1000<br />

800<br />

1100<br />

900<br />

1200<br />

1000<br />

1300<br />

1100<br />

1400<br />

1200<br />

1500<br />

L<br />

L<br />

M<br />

M<br />

H<br />

H<br />

038 800 1000 1100 1300 1500 1600 1800<br />

0.75<br />

w/1hp* L M H<br />

049 0.50<br />

650 800 900 1050 1150 1250 1350 1450 1550<br />

L M H<br />

049 800 900 1000 1200 1400 1600 1700 1850 2000 2200 2300 2400<br />

0.75<br />

w/1hp* L M H<br />

064<br />

072<br />

0.75<br />

0.75<br />

800<br />

800<br />

950<br />

950<br />

1100<br />

1100<br />

1300<br />

1300<br />

1500<br />

1500<br />

1750<br />

1750<br />

1950<br />

1950<br />

2100<br />

2100<br />

2300<br />

2300<br />

L<br />

L<br />

M<br />

M<br />

H<br />

H<br />

Factory settings are at recommended L-M-H DIP switch locations<br />

M-H settings MUST be located within boldface CFM range<br />

Lowest and Highest DIP switch settings are assumed to be L and H respectively<br />

CFM is controlled within ±5% up to the maximum ESP<br />

Max ESP includes allowance for wet coil and standard filter<br />

5/30/06<br />

5/30/06<br />

19