PREMIUM G SERIES INSTALLATION MANUAL<br />

Heat of Extraction/Rejection<br />

Single Speed<br />

Model<br />

gpm<br />

Heat of Extraction (kBtuh)<br />

Heat of Rejection (kBtuh)<br />

30°F 50°F 70°F 90°F 30°F 50°F 70°F 90°F 110°F<br />

1.5 7.4 9.6 12.5 16.9 16.5 15.8<br />

012<br />

2.5 5.9 7.7 10.1 12.7 17.3 16.9 16.4 15.9 16.0<br />

3.5 6.1 8.1 10.6 12.9 17.4 16.9 16.4 16.0 16.1<br />

3.0 11.4 13.9 19.1 23.0 21.6 20.5<br />

018<br />

4.0 10.1 12.2 14.8 19.5 21.1 23.3 21.7 20.5 20.1<br />

5.0 10.4 13.1 15.8 19.8 21.2 23.6 21.9 20.7 20.1<br />

3.0 14.2 18.8 22.9 28.8 28.5 26.1<br />

022<br />

4.5 10.3 15.0 19.9 24.0 26.2 29.0 28.6 26.1 24.8<br />

6.0 10.5 15.4 20.2 24.5 26.4 29.2 28.6 26.2 24.8<br />

4.0 20.0 26.0 31.0 35.1 35.4 33.1<br />

030<br />

6.0 14.6 20.8 27.1 32.3 32.6 35.0 35.3 33.0 29.3<br />

8.0 14.9 21.3 27.6 32.8 32.9 35.3 35.5 33.2 29.4<br />

5.0 23.8 31.3 37.6 41.5 42.7 40.8<br />

036<br />

7.0 17.7 24.9 32.6 39.2 34.9 41.4 42.6 40.7 38.0<br />

9.0 18.1 25.5 33.2 39.8 35.3 41.8 42.9 40.9 38.2<br />

5.0 27.2 33.7 40.0 50.2 51.2 48.8<br />

042<br />

8.0 21.0 28.5 35.5 42.4 46.9 50.4 51.5 49.1 45.9<br />

11.0 21.4 29.3 36.6 43.9 47.2 50.7 51.8 49.3 45.9<br />

6.0 35.1 43.9 51.2 60.6 60.5 57.0<br />

048<br />

9.0 26.8 36.7 46.3 54.3 56.2 60.8 60.9 57.4 53.8<br />

12.0 27.3 37.7 47.7 56.2 56.5 61.1 61.1 57.5 53.8<br />

9.0 44.1 56.3 65.1 83.1 81.3 76.5<br />

060<br />

12.0 31.5 45.5 57.5 69.1 80.2 82.9 81.6 76.3 71.9<br />

15.0 32.6 46.4 59.9 70.0 80.8 83.2 81.2 76.5 72.0<br />

12.0 52.4 66.9 78.1 91.1 89.5 83.0<br />

070<br />

15.0 37.9 53.7 69.8 82.9 83.4 91.2 89.4 82.7 76.8<br />

18.0 38.1 54.3 70.9 84.8 83.8 91.9 90.3 83.6 77.6<br />

NOTE: Operation not recommended in shaded areas. 2/13/12<br />

Dual Capacity<br />

Model<br />

gpm<br />

Heat of Extraction (kBtuh)<br />

Heat of Rejection (kBtuh)<br />

30°F 50°F 70°F 90°F 30°F 50°F 70°F 90°F 110°F<br />

3.0 14.0 18.8 22.8 26.7 26.6 24.3<br />

Part Load 5.0 10.2 14.8 19.8 24.0 24.7 26.8 26.7 24.2 22.2<br />

026<br />

7.0 10.3 15.1 20.1 24.4 25.0 27.0 26.7 24.3 22.2<br />

4.0 18.6 24.3 29.6 34.8 34.9 33.4<br />

Full Load 6.0 14.0 19.7 25.7 31.1 33.6 34.9 35.0 33.3 31.1<br />

8.0 14.3 20.1 26.1 31.7 33.9 35.1 35.1 33.4 31.1<br />

4.0 17.6 22.8 27.5 35.3 34.5 32.4<br />

Part Load 6.0 12.6 18.3 24.0 29.2 32.5 35.6 34.7 32.5 30.3<br />

038<br />

8.0 13.6 19.3 24.6 29.2 33.0 36.1 35.2 32.9 30.7<br />

5.0 25.1 31.4 35.9 48.3 48.5 45.8<br />

Full Load 7.0 18.8 26.2 33.1 38.4 45.2 48.8 49.2 46.7 43.6<br />

9.0 19.2 26.9 34.1 39.7 45.5 49.1 49.6 47.0 43.8<br />

5.0 23.2 28.6 32.7 47.4 48.5 46.2<br />

Part Load 8.0 18.4 25.6 31.7 36.5 42.9 47.5 48.3 45.6 42.2<br />

049<br />

11.0 19.1 26.6 33.4 38.9 42.4 47.5 48.7 46.5 43.3<br />

6.0 33.5 40.8 46.2 63.4 63.2 59.0<br />

Full Load 9.0 26.1 34.8 43.0 49.3 59.1 63.5 63.9 60.1 55.0<br />

12.0 26.7 35.8 44.4 51.1 59.3 63.7 64.3 60.3 55.3<br />

6.0 32.6 41.0 48.0 60.6 59.4 55.5<br />

Part Load 10.0 22.8 32.9 42.7 51.8 56.5 60.5 59.5 55.8 52.2<br />

064<br />

14.0 23.9 34.1 43.6 51.9 56.3 60.5 59.6 56.1 52.5<br />

8.0 43.9 56.4 69.0 81.0 82.9 76.5<br />

Full Load 12.0 34.5 47.0 58.9 70.2 73.7 81.5 83.4 76.7 71.4<br />

16.0 34.9 47.9 60.7 73.1 74.1 82.0 83.8 77.2 71.5<br />

10.0 36.8 47.0 55.3 68.4 67.9 63.2<br />

Part Load 13.0 25.5 37.1 49.1 59.7 62.4 68.3 67.9 63.5 58.8<br />

072<br />

16.0 27.1 38.6 50.0 59.8 61.9 68.3 68.2 63.8 59.1<br />

12.0 50.2 65.1 78.2 89.6 88.1 84.6<br />

Full Load 15.0 38.7 53.7 67.8 79.4 80.9 90.0 91.0 84.9 77.8<br />

18.0 39.1 54.7 70.0 82.7 81.5 90.6 91.5 85.3 78.1<br />

NOTE: Operation not recommended in shaded areas. 2/13/12<br />