Model <strong>5204</strong> Fire Control/Communicator Installation ManualThe following formula was used to calculate the figures in Table 4-2:I = [AH ÷ H] x 0.70Where: I = Standby currentAH = Ampere-hour rating of batteryH = Standby hours0.70 = A constant used to de-rate the battery to assure a 5-year life.6. Ensure that the total alarm current you calculated, including current for the panel itself,does not exceed 3.5 A. This is the maximum alarm current allowable, whether the panelprovides 12 V or 24 V of smoke power.4-6 150644