11.07.2015 Views

warning - Coastal Winair

warning - Coastal Winair

warning - Coastal Winair

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Typical System Piping DiagramPrimary Secondary Loop with 4-way Motorized Valve with Circulator in Secondary Loop OnlyLow Temperarure with Low Mass Heat Emittersor High Temperature with High or Low Mass Heat Emitters1Back FlowPreventerGlobeValvePressureGaugeGlobeValveGlobeValvePressureReducerAirSeparatorCirculatorPumpSupply WaterTemperatureSensorReliefValveSupplyExhaustVent2Expansion Tank4-WayMotorized ValveReturn WaterTemperatureSensorReturnBoilerReturn water temperaturemust be above 110 O F12NOTES:Protects boiler from too low return water temperature and condensation.Locate the circulator inlet close to the connection point of the expansion tank, but allow at least the equivalent of 10 to 12 pipediameters between the circulator pump inlet and the expansion tank to reduce the possibility of pump noise and facilitate airremoval.Heat Emitter18-CG03D1-416

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!