5. Technical Data5.1 AIR DISTRIBUTION (NORMAL OPERATION)STALE AIRTO OUTSIDEFRESH AIRTO BUILDINGSTALE AIRTO OUTSIDESTALE AIRFROM BUILDINGVF0016 SOLO VF0017DUOFRESH AIRFROM OUTSIDESTALE AIRFROM BUILDINGFRESH AIRFROM OUTSIDEFRESH AIRTO BUILDING5.2 AIR DISTRIBUTION (DEFROST AND/OR FILTRATION MODE)FILTERED AIRTO BUILDINGSTALE AIRFROM BUILDINGVF0018SOLOSTALE AIRFROM BUILDINGVF0019DUOFILTERED AIRTO BUILDING5.3 DEFROST CYCLES TABLESSOLO unitsOutside Temperature Defrost Cycles Extended Defrost CyclesCelcius (°C)-5-15-27Fahrenheit (°F)235-17Defrosting (min.)666Operation time (min.)between each defrost cycleDUO unitsOutside Temperature Defrost Cycles Extended Defrost CyclesCelcius (°C)-5-15-27Fahrenheit (°F)235-17Defrosting (min.)999603220Operation time (min.)between each defrost cycle603220Defrosting (min.)101010Defrosting (min.)101010Operation time (min.)between each defrost cycle302015Operation time (min.)between each defrost cycle302015NOTE:THE SOLO AND DUO PERFORMANCE CHARTS ARE LISTED ON THE SPECIFICATION SHEETS OF THESE UNITS.VISIT OUR WEBSITE AT WWW.VENMAR.CA TO ACCESS THOSE DOCUMENTS.8