-- SET SYS TEMP.1 -120 F[ ]BACK SAVE-- AT OD TEMP.1 ---60 F[ ]BACK SAVE-- SET SYS TEMP.2 -170 F[ ]BACK SAVE-- AT OD TEMP.2 ---0 F[ ]BACK SAVEWater Temperature (in °F)Point1: System=120°F Point2: System=170°FOudoor=60°FOudoor=0°F180Max Target170160150140130120110Point1Customized Reset RatioMin TargetPoint210070 60 50 40 30 20 10 0 -10 -20Outdoor Temperature (in °F)Custom Reset Ratio----- SET POINT -----ººººCºº70 FButton: MENU/Set Point [ ] BACK SAVEsystem temperature around the Set point. Stage Settings. SAVE button will continue to the Outdoor Cutoff setting option. Shutdown by EMS-- OUTDOOR CUTOFF --ºººº70 FHold Button: MENU/Set Point/Outdoor Cutoff [ ]Hold Button: MENU//Outdoor Cutoff BACK SAVEif the outdoor sensor is installed, the Outdoor Cutoff screen will automatically appearafter the temperature Set Point has been selected. boiler stages to hold the calculated temperature. delay. temperature and the burner stages will be active to hold the target water temperature. ººººººHold Button: MENU//Offset of the Outdoor temperature, or the Reset Ratio that has been selected, when the Offsetsetting is changed, that change is directly added to or subtracted from the calculatedchanged from 0° to 10° (an increase of 10°), the Set Point would increase to 140°F.-- TARGET OFFSET ---+0 F[ ]BACK SAVE22