Process Control Instruction 349Runtime ErrorsError code 0036 appears in the status file when a PID instruction runtimeerror occurs. Code 0036 covers the following PID error conditions, eachof which has been assigned a unique single byte code value that appearsin the MSB of the second word of the control block. The error code is alsodisplayed on the PID Setup Screen in RSLogix 500/RSLogix Micro.Error Code Description of Error Condition or Conditions Corrective Action11H1. Loop update timeChange loop update time 0 < D t < 1024D t > 10242. Loop update timeD t = 012H13H14HProportional gainK c < 0Integral gain (reset)T i < 0Derivative gain (rate)T d < 0Change proportional gain K c to 0 < K cChange integral gain (reset) T i to 0 < T iChange derivative gain (rate) T d to 0 < T d15H Feed Forward Bias (FF) is out-of-range. Change FF so it is within the range -16383…+16383.23HScaled setpoint minChange scaled setpoint min MinS toMinS > Scaled setpoint max MaxS-32768 < MinS < MaxS < +3276731HIf you are using setpoint scaling andMinS > setpoint SP > MaxS, orIf you are using setpoint scaling, then changethe setpoint SP to MinS < SP < MaxS, orIf you are not using setpoint scaling and0 > setpoint SP > 16383,If you are not using setpoint scaling, then changethe setpoint SP to 0 < SP < 16383.then during the initial execution of the PID loop, this erroroccurs and bit 11 of word 0 of the control block is set.However, during subsequent execution of the PID loop ifan invalid loop setpoint is entered, the PID loop continuesto execute using the old setpoint, and bit 11 of word 0 ofthe control block is set.41H Scaling Selected Scaling Deselected Scaling Selected Scaling Deselected1. Deadband < 0, or 1. Deadband < 0, or Change deadband to Change deadband to0 < deadband 2. Deadband > 16383(MaxS - MinS) < 16383(MaxS – MinS)51H52H1. Output high limit < 0, or2. Output high limit > 1001. Output low limit < 0, or2. Output low limit > 100Change output high limit to0 < output high limit < 100Change output low limit to0 < output low limit < output high limit < 10053H Output low limit > output high limit Change output low limit to0 < output low limit < output high limit < 100Publication <strong>1766</strong>-<strong>RM001A</strong>-<strong>EN</strong>-P - October 2008

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!