Communications Instructions 437If the target device is a ControlLogix, FlexLogix or CompactLogixcontroller with an Ethernet interface, then enter in the interface’s IPaddress in the first row of the “To Address” column, press the computer’sInsert key to add a hop. Select ControlLogix Backplane and enter in thebackplane slot number for the controller (always 0 for FlexLogix andCompactLogix, 0-16 for ControlLogix) in the second row of the “ToAddress” column as shown below under the MultiHop tab.If the target device is a ControlLogix controller with an ControlNetinterface, then enter in the interface’s IP address of the 1756 <strong>EN</strong>ET modulein the first row of the “To Address” column, press the computer’s Insertkey to add a hop. Select ControlLogix Backplane and enter in thebackplane slot number of the ControlNet Interface module (0-16 forControlLogix) in the second row of the “To Address” column as shownbelow under the MultiHop tab. Double click on the From Device underthe ControlLogix Backplane and select the 1756-ControlNet Interface.Enter the address of the ControlNet Interface using 1747-KFC15.Publication <strong>1766</strong>-<strong>RM001A</strong>-<strong>EN</strong>-P - October 2008