13.07.2015 Views

1766-RM001A-EN-P MicroLogix 1400 Programmable Controllers ...

1766-RM001A-EN-P MicroLogix 1400 Programmable Controllers ...

1766-RM001A-EN-P MicroLogix 1400 Programmable Controllers ...

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

ASCII Instructions 365String Data File StructureString ElementBit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00Word upper byte lower byte0 String Length - number of characters (range is from 0…82)1 character 0 character 12 character 2 character 3↓ ↓ ↓40 character 78 character 7941 character 80 character 81Addressing String FilesThe addressing scheme for the string data file is shown below.Table 2:Format ExplanationST String fileSTf:e.s f File number The valid file number range is from 3…255.: Element delimitere Element number The valid element number range is from 0…255.Each element is 42 words in length as shown in .. Subelement delimiters Subelement number The valid subelement number range is from 0…41.You can also specify .L<strong>EN</strong> for word 0 and .DATA[0] through .DATA[40] for words 1…41.Examples:ST9:2ST17:1.L<strong>EN</strong>ST13:7.DATA[1]The subelement represents a word address.String File 9, Element 2String File 17, Element 1, L<strong>EN</strong> VariableString File 13, Element 7, word 2 (characters 2 and 3)Publication <strong>1766</strong>-<strong>RM001A</strong>-<strong>EN</strong>-P - October 2008