402 Communications InstructionsMessage File Target Location InformationTarget Device = CIP GenericSub-ElementName Description ParameterSizeUserProgramAccess12 Target Class Y Word read only13 Target Instance Y Word read/write14 CIP Send Data Count Y Word read/write15 Internal Physical Address ofCIP Send Data TableAddress operandY Word read onlyThe Control Bits, Sub-Element 16, of the MSG File Element are definedbelow:Message File Sub-Element 16 - Control BitsBit Address Description Parameter Size UserProgram15 MG11:0.0/<strong>EN</strong> EnableAccessN bit read/write1=MSG enabled0=MSG not enabled9…1Reserved N bit read/write48 MG11:0.0/TO Time OutN bit read/write1=MSG time out by user0=no user MSG time out1…7 Reserved N bit read/write0 MG11:0.0/BK Break ConnectionN bit read/writeFor Channel 1,1=MSG Connection closed byuser0=MSG Connection not closedby userThe Status Bits, Sub-Element 17, of the MSG File Element are definedbelow.Publication <strong>1766</strong>-<strong>RM001A</strong>-<strong>EN</strong>-P - October 2008