CIVIL APPROVALS - FIRE<strong>Hawke</strong>Civil <strong>Transit</strong> <strong>System</strong>1. Frame cast into wall or floor.2. For frames bolted to walls or floors, 966<strong>Hawke</strong> intumescent mastic to be used behindthe flange or frame.100 mm150 mmFIRE BATT. DENSITY110 kg/ m 3 MINIMUMSHEREDDED FIRE BATTCivil Approvals - FireIn order to limit the spread of fire,regulations generally demand thatbuildings are divided intocompartments each offering a degreeof fire spread resistance.Fig 3.100 mm100 mm150 mm3. For periods in excess of 120 mins, it may be necessary for frames to be mountedon both sides of the wall or to be insulated as shown. (Contact <strong>Hawke</strong> for latest techinfo).<strong>Hawke</strong> have tested the <strong>Transit</strong>system extensively to National andInternational standards100 mm150 mmFIRE BATT. DENSITY110 kg/ m 3 MINIMUMSHEREDDED FIRE BATT200 nominal4. For certain conditions it may be necessary to restrict the average temperature riseabove ambient on the unexposed face of a compartment wall or floor. Since the metalused in cable construction readily transmits heat, the following installation methods arerecommended to provide compliance for up to 360 minutes. (See Figs. 3 and 4 above).www.hawke-hts.com17