Nominal output 13.5 m/s<br />

Cut-out wind speed 25 m/s<br />

Tower Tubular cone-shaped<br />

Height 30 m<br />

<strong>Co</strong>ntrol system Made <strong>for</strong> VESTAS<br />

Diesel engines: 2 engines<br />

Power of each 160 KVA<br />

<strong>Co</strong>nnection Mechanically through an electromagnetic<br />

clutch to the flywheel<br />

Flywheel Each can deliver a half of the envisaged peak<br />

power demand -100 kW- during 30 seconds<br />

Frequency minimum level<br />

48 Hz<br />

allowed<br />

The three-bladed wind driven generator, with variable pitch and constant velocity,<br />

and an induction type electricity generating machine, with double coil winding of six<br />

and eight pairs of poles, respectively, enabling the operation of the generator at two<br />

different wind speed regimes. Although the initial nominal power of the generator<br />

was 225 kW, at the beginning of 2001 this nominal power was restricted to 130 kW<br />

acting on the angle of pitch of the blades of the rotor.<br />

c. Experiences and Lessons Learnt<br />

The main observation during system operation, concerned with the mismatch<br />

between the power output from the wind generator and the load of the system. The<br />

generated energy exceeds the energy demand at the site, and hence a large dump<br />

load is required in order to make up with the excess power.<br />

The need to limit the nominal power of the wind-driven generator was due to the fact<br />

that the actual energy demand turned out to be lower than had been estimated and<br />

far less than the generator is capable of supplying at nominal power (225 kW). As a<br />

result, when the wind speeds exceeded the 10 m/s at the height of the rotor shaft,<br />

the generator would shut down due to over-frequency. Though it would have been<br />

advantageous to be able to set variable nominal power limits lower than 130 kW as<br />

also the manufacturer is advised.<br />

The system began its operation in May 1995. However, given the fact that the growth<br />

<strong>for</strong>ecasts <strong>for</strong> the community as estimated by the Local <strong>Co</strong>uncil of Pajara turned out<br />

to be inaccurate and given the incorrect technical and economic management of the<br />

WP2 <strong>ADU</strong>-<strong>RES</strong> 35