3-6 Programming and Parameters<br />

Display Group (continued)<br />

d014 [Dig In Status] Related Parameter(s): t201, t202<br />

Status of the control terminal block digital inputs.<br />

1 = Input Present, 0 = Input Not Present<br />

Digital In1 Sel (I/O Terminal 05) Bit 0<br />

Digital In2 Sel (I/O Terminal 06) Bit 1<br />

Reserved Bit 2<br />

Reserved Bit 3<br />

Values Default Read Only<br />

Min/Max: 0/1<br />

Display: 1<br />

d015 [Comm Status] Related Parameter(s): C302 - C306<br />

Status of the communications ports.<br />

1 = Condition True, 0 = Condition False<br />

Receiving Data Bit 0<br />

Transmitting Data Bit 1<br />

<strong>RS485</strong> (<strong>DSI</strong>) Based Option Connected Bit 2<br />

(Allen-Bradley devices only.)<br />

Communication Error Occurred Bit 3<br />

Values Default Read Only<br />

Min/Max: 0/1<br />

Display: 1<br />

d016 [Control SW Ver]<br />

Main Control Board software version.<br />

Values Default Read Only<br />

Min/Max: 1.00/99.99<br />

Display: 0.01<br />

d017 [Drive Type]<br />

Used by Rockwell Automation field service personnel.<br />

Values Default Read Only<br />

Min/Max: 1001/9999<br />

Display: 1