3-8 Programming and Parameters<br />

Basic Program Group<br />

P101 [Motor NP Volts] Related Parameter(s): d004, A453<br />

Stop drive before changing this parameter.<br />

Set to the motor nameplate rated voltage.<br />

Values Default Based on Drive Rating<br />

Min/Max: 20/Drive Rated Voltage<br />

Display: 1 VAC<br />

P102 [Motor NP Hertz] Related Parameter(s): A453, A444<br />

Stop drive before changing this parameter.<br />

Set to the motor nameplate rated frequency.<br />

Values Default 60 Hz<br />

Min/Max: 10/400 Hz<br />

Display: 1 Hz<br />

P103 [Motor OL Current] Related Parameter(s): P111, t221, A441, A444, A448, A437<br />

Set to the maximum allowable motor current.<br />

The drive will fault on an F7 Motor Overload if the value of this parameter is exceeded by 150% for 60<br />

seconds or 200% for 3 seconds.<br />

Values Default Based on Drive Rating<br />

Min/Max: 0.0/(Drive Rated Amps × 2)<br />

Display: 0.1 Amps<br />

P104 [Minimum Freq] Related Parameter(s): d001, d002, d013, P105, t211, t213, A438<br />

Sets the lowest frequency the drive will output continuously.<br />

Values Default 0.0 Hz<br />

Min/Max: 0.0/400.0 Hz<br />

Display: 0.1 Hz<br />

P105 [Maximum Freq]<br />

Stop drive before changing this parameter.<br />

Sets the highest frequency the drive will output.<br />

Values Default 60 Hz<br />

Min/Max: 0/400 Hz<br />

Display: 1 Hz<br />

Related Parameter(s): d001, d002, d013, P104, A404,<br />

t212, t214, A438