Calculating example<br />

If you want to calculate the modbus register offset Y to control an I/O Module at<br />

address A then:<br />

for P-<strong>Bus</strong> 1: Y = 512 + A * 8<br />

and<br />

for P-<strong>Bus</strong> 2: Y = 2816 + A * 8<br />

in which the registers:<br />

Y + 0 to Y + 3 are the read registers 0 – 3 of the I/O Module at address A and<br />

Y + 4 to Y + 7 are the write registers 0 – 3 of the I/O Module at address A.<br />

Now, suppose you’ll want to control an I/O Module at address 7 on P-<strong>Bus</strong> 2 then:<br />

Y = 2816 + 7 * 8 = 2872.<br />

The read registers 0 – 3 of the I/O Module at address 7 are: 2872 – 2875 and<br />

The write registers 0 – 3 of the I/O Module at address 7 are: 2876 – 2879.<br />

An easy tool for calculating the modbus-addresses is available on our website:<br />

www.persy.nl and can be found under document number: PCS018x<br />

diagnostic functions<br />

Detailed mapping of the diagnostic functions:<br />

Dec. Hex. Description<br />

0 0x00 Device Status<br />

1 – 7 0x01 – 0x07 Not used<br />

8 0x08 PBUS 1 Current Operating Mode<br />

9 0x09 PBUS 1 Error Status<br />

10 0x0A PBUS 1 Number of I/O Modules present<br />

11 0x0B PBUS 1 Number of load units present<br />

12 – 15 0x0C – 0x0F Not used<br />

16 0x10 PBUS 2 Current Operating Mode<br />

17 0x11 PBUS 2 Error Status<br />

18 0x12 PBUS 2 Number of I/O Modules present<br />

19 0x13 PBUS 2 Number of load units present<br />

20 – 255 0x14 – 0xFF Not used<br />

Device Status:<br />

0 = normal operations<br />

1 = firmware upgrade mode<br />

2 = reset<br />

3 = hardware failure, gateway need to be reset or exchanged<br />

PBUS Current Operating Mode:<br />

0 = not used<br />

1 = slave<br />

2 = master<br />

PBUS Error Status:<br />

Bit Description<br />

0 Set = general failure, gateway need to be reset or exchanged<br />

1 Set = overload<br />

2..15 not used<br />

16/17<br />

Persy Control Services B.V.<br />

Netherlands<br />

<strong>PBGW2.128</strong> – P-bus <strong>Gateway</strong><br />

PCS0113en<br />

02.2009