P-Bus Gateway Firmware PBGW2.128 Version 1.61
P-Bus Gateway Firmware PBGW2.128 Version 1.61 - Persy
P-Bus Gateway Firmware PBGW2.128 Version 1.61 - Persy
- No tags were found...
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Device Setup<br />
Port Settings<br />
In this page you can make changes in the RS-232 and RS-485 configuration. This<br />
configuration is being applied to the Modbus RTU protocol when enabled in the<br />
Modbus RTU Server Protocol Settings. Match these settings to the device the<br />
gateway communicates with (Modbus Client).<br />
The possible settings are:<br />
Baudrate: 110, 300, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200<br />
Databits: 8<br />
Parity: None, Even, Odd<br />
Stopbits: 1, 2<br />
Handshaking: None, RTS/CTS<br />
The factory defaults for RS-232 are: 9600, 8, N, 1, No Handshaking<br />
The factory defaults for RS-485 are: 9600, 8, N, 1.<br />
If RTS/CTS handshaking is used with RS-232, pin 7 & 8 of the DSUB-9 connector<br />
(X5) have to be connected also.<br />
NOTE:<br />
!! When applying the settings (‘Apply Settings’) all communications could be<br />
interrupted temporarily.<br />
6/17<br />
Persy Control Services B.V.<br />
Netherlands<br />
<strong>PBGW2.128</strong> – P-bus <strong>Gateway</strong><br />
PCS0113en<br />
02.2009