Device Setup<br />

Port Settings<br />

In this page you can make changes in the RS-232 and RS-485 configuration. This<br />

configuration is being applied to the Modbus RTU protocol when enabled in the<br />

Modbus RTU Server Protocol Settings. Match these settings to the device the<br />

gateway communicates with (Modbus Client).<br />

The possible settings are:<br />

Baudrate: 110, 300, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200<br />

Databits: 8<br />

Parity: None, Even, Odd<br />

Stopbits: 1, 2<br />

Handshaking: None, RTS/CTS<br />

The factory defaults for RS-232 are: 9600, 8, N, 1, No Handshaking<br />

The factory defaults for RS-485 are: 9600, 8, N, 1.<br />

If RTS/CTS handshaking is used with RS-232, pin 7 & 8 of the DSUB-9 connector<br />

(X5) have to be connected also.<br />

NOTE:<br />

!! When applying the settings (‘Apply Settings’) all communications could be<br />

interrupted temporarily.<br />

6/17<br />

Persy Control Services B.V.<br />

Netherlands<br />

<strong>PBGW2.128</strong> – P-bus <strong>Gateway</strong><br />

PCS0113en<br />

02.2009