07.12.2012 Views

Catalogue ELS/SV - Lumentron Electronic Kft.

Catalogue ELS/SV - Lumentron Electronic Kft.

Catalogue ELS/SV - Lumentron Electronic Kft.

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>ELS</strong> - <strong>SV</strong><br />

Specification text and technical data<br />

850<br />

785<br />

INOTEC <strong>ELS</strong>-<strong>SV</strong> emergency lighting system<br />

with Joker-technology, for the supply and<br />

monitoring of up to 60 safety- or exit<br />

luminaries. Each outgoing circuit is for 15<br />

luminaries in maintained, non-maintained or<br />

switched maintained mode either mixed or in<br />

one mode on the line. The <strong>ELS</strong>/<strong>SV</strong> system<br />

incorporates:<br />

- battery for 1h or 3h duration<br />

- charger<br />

- 4 converters, each suitable for 15 monitored<br />

luminaries, max. converter load 120W.<br />

- control module with two-line liquid crystal<br />

display for status information in national<br />

language<br />

- light-switch-monitor and Joker- technology<br />

- delay on mains return option (0 - 15 min)<br />

Mains supply: 230/240 V AC<br />

Output voltage mains: 230/240 V AC<br />

Output voltage battery: 220 V DC<br />

Rated duration: 1h or 3h<br />

Protection class I, protection category IP 40<br />

Max. permissible ambient temp. : -5°C to +40°C<br />

Weight:<br />

With 17 Ah batteries 32kg<br />

With 34 Ah batteries 46kg<br />

325 100<br />

400<br />

Mechanical design:<br />

Powder coated (RAL 7032) sheet steel housing<br />

with separate battery compartment.<br />

OCTA-aluminium profile door with clear<br />

polycarbonate inlay, lhs door hinges. Separate<br />

internal covers for battery-, terminal- and<br />

electronic compartment. Block diagram with<br />

technical data on electronic compartment<br />

cover. Housing with internal earth contacts.<br />

Cable inlets top. Battery and terminal /<br />

electronics compartment with ventilation<br />

slots. The <strong>ELS</strong>-<strong>SV</strong> is suitable for wall mounting<br />

(fixing details 325 x 765 mm; hole ø 6 mm).<br />

Total ( H x W x D) 870 x 420 x 105 mm<br />

870<br />

420<br />

105<br />

Electrical design:<br />

Supply- (max. 1 x 4 mm² ) and outgoing<br />

circuits (max. 2 x 2,5 mm² ) are prewired to<br />

terminals located on the central terminal rail.<br />

The cable inlets on the top of the enclosure<br />

are predrilled and closed with rubber blind<br />

plugs M20. Battery- and mains fuses for<br />

charger and each converter are included.<br />

Creepage- and clearance distances are in line<br />

to IEC standards.<br />

Three volt-free contacts (3xno) for the remote<br />

failure/status indication are available.<br />

Maintained and non-maintained circuits can<br />

be freely programmed via the control module.<br />

Mixed operation of maintained-,<br />

non-maintained- and switched maintained<br />

luminaries on any final end circuit<br />

(Joker-technology) is always possible.<br />

24 V monitoring loop<br />

Each <strong>ELS</strong>-<strong>SV</strong> has the terminals to connect<br />

external phase monitors (DPÜ). They are used<br />

to monitor sub-distributions for general<br />

lighting or individual lighting circuits. The max.<br />

cable run allowed is 2000m with 1,5 mm².<br />

Charger 3A:<br />

Temperature controlled constant voltage<br />

charger, current limited, with boost charge<br />

function. Battery voltage monitoring and time<br />

-controlled trickle charge function. Chargers<br />

failures are visual via a red "charge failure" LED<br />

on the left side of the display area.<br />

Recharge time: